Results 1 to 8 of 8
  1. #1
    Join Date
    Oct 2003
    Location
    Rockwall Texas
    Posts
    4,521

    Default Condensing Unit Clearances

    I didn't know if post should be HVAC, Plumbing (Gas lines) or Pools.

    We once had this discussion but can't seem to find it while searching.

    As you can see in my pic below the gas line and the pool heater is against the condensing unit.

    Comments are welcomed.

    rick

    Similar Threads:
    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    Last edited by Rick Hurst; 09-28-2009 at 08:05 PM. Reason: brain fart
    Member Benefits1

  2. #2
    Join Date
    Mar 2007
    Location
    Plano, Texas
    Posts
    4,245

    Default Re: Condensing Unit Clearances

    I'll bet it is wrong on manufacturer's clearances on both the a/c and pool heater.

    Jim Luttrall
    www.MrInspector.net
    Plano, Texas

  3. #3
    Join Date
    Mar 2007
    Location
    Atlanta, Georgia
    Posts
    1,088

    Default Re: Condensing Unit Clearances

    Most a/c manufacturers require a min. of 12 inch clearance along the sides and 48 inches overhead.

    Two units side by side would require a combined clearance of 24 inches between units to allow for proper air flow.

    Here is a link to a question I asked on Jerry's forum regarding access to electrical connections for an a/c and it spun off into clearances between and around units.
    http://www.askcodeman.com/viewtopic.php?f=3&t=141

    "The Code is not a peak to reach but a foundation to build from."

  4. #4
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: Condensing Unit Clearances

    Regarding the gas line, no clearances, however, regarding everything else, there would be a minimum of 12" on each side and 30" (36" when connected to electrical power) on the service access side.

    Also, the unit(s) are not allowed under the overhang roof runoff (installing a gutter is easier than moving the unit).

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  5. #5
    Join Date
    Oct 2003
    Location
    Rockwall Texas
    Posts
    4,521

    Default Re: Condensing Unit Clearances

    Quote Originally Posted by Jerry Peck View Post
    Regarding the gas line, no clearances, however, regarding everything else, there would be a minimum of 12" on each side and 30" (36" when connected to electrical power) on the service access side.

    Also, the unit(s) are not allowed under the overhang roof runoff (installing a gutter is easier than moving the unit).

    Jerry's comment above got me to wondering how many inspectors actually write up the condensing unit being located directly under the eaves with no water diverter on the roof above or guttering.

    Some homes I find the water diverter flashing on the roof, many do not.

    rick


  6. #6
    Ron Bibler's Avatar
    Ron Bibler Guest

    Default Re: Condensing Unit Clearances

    Quote Originally Posted by Rick Hurst View Post
    Jerry's comment above got me to wondering how many inspectors actually write up the condensing unit being located directly under the eaves with no water diverter on the roof above or guttering.

    Some homes I find the water diverter flashing on the roof, many do not.

    rick
    Rick I call it all the time along with the 12" air space.
    These are some of the things that never get corrected.

    Kind of like a Zinsco panel... most of the inspectors in my area don't say much about them.

    Best

    Ron


  7. #7
    Join Date
    Mar 2007
    Location
    Lake Barrington, IL
    Posts
    1,367

    Default Re: Condensing Unit Clearances

    Quote Originally Posted by Ron Bibler View Post
    Rick I call it all the time along with the 12" air space.
    These are some of the things that never get corrected.
    WHAT! People ignore home inspection reports? Tell me it ain't so.

    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    Eric Barker, ACI
    Lake Barrington, IL

  8. #8
    Join Date
    Mar 2007
    Location
    Near Philly, Pa.
    Posts
    1,682

    Question Re: Condensing Unit Clearances

    gas piping:
    -is there protection around that galv. steel pipe? Consider cathodic protection.
    -how does your AHJ interpret the sediment trap requirement for outdoor applications?
    -should replace the shutoff with modern listed ball valve. Those ground key valves either seize up or leak. Not allowed by our gas utility around here.
    -merchant coupling should be replaced as it is too weak. Need Sch. 40 coupling.
    -is there a ground union inside the appliance cabinet?
    -what is there to protect the gas pipe from a lawn mower? physical protection.

    Keep the fire in the fireplace.

Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •