    What is the clearance on this type of venting. There have been previous posts but I was unable to locate the info.

    Similar Threads:
    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    OREP Insurance

  2. #2
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: Flex vent

    IF single wall - 6".

    IF Type B - 1".

    With that tape on there (which is not allowed either) I could not tell which it was.

    Also, that is not allowed to "go into" that wall. (Besides the hole needed to be sealed for energy and fireblocking purposes.)

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  3. #3
    mathew stouffer's Avatar
    mathew stouffer Guest

    Default Re: Flex vent

    Yeah I know, and of course the owner was there and I could not try to remove it. The vent felt pretty thick, I could not squeeze it and cause a depression.


  4. #4
    Join Date
    Aug 2007
    Location
    Memphis TN.
    Posts
    4,311

    Default Re: Flex vent

    Quote Originally Posted by mathew stouffer View Post

    What is the clearance on this type of venting. .
    .
    This Product is made as Single Wall and Double Wall so it would depend on which one is Installed.

    Your photo shows direct contact so it would be an improper installation in either product configuration.
    .
    Insul-Vent Double Wall Insulated Vent Connector Kit - Gas-Insul-Vent Flexible Vent Connector Systems - Nova Flex
    .

    It Might have Choked Artie But it ain't gone'a choke Stymie! Our Gang " The Pooch " (1932)
    Billy J. Stephens HI Service Memphis TN.