Results 1 to 20 of 20
  1. #1
    Join Date
    Sep 2008
    Location
    so so, California
    Posts
    1,867

    Default Condensate line question

    I have two FAU's in the attic. Anyone know if the two primary condensate drain lines can be connected together? They are trapped at the FAU and drain into the bathroom sink drain-before the trap.

    Similar Threads:
    Last edited by Marc M; 11-30-2009 at 11:08 PM.
    Inspection Referral

  2. #2
    Join Date
    Mar 2007
    Location
    Plano, Texas
    Posts
    4,245

    Default Re: Condensate line question

    A 3/4 inch drain line is good for up to 20 tons. I don't understand how you would connect two units "in-line" but if you mean two lines joined and then run to the drain, I see nothing wrong with that.

    Jim Luttrall
    www.MrInspector.net
    Plano, Texas

  3. #3
    Join Date
    Sep 2008
    Location
    so so, California
    Posts
    1,867

    Default Re: Condensate line question

    Roger that...thanks


  4. #4
    A.D. Miller's Avatar
    A.D. Miller Guest

    Default Re: Condensate line question

    WTF is an FAU?


  5. #5
    Join Date
    Mar 2007
    Location
    Philadelphia PA
    Posts
    3,177

    Default Re: Condensate line question

    Quote Originally Posted by A.D. Miller View Post
    WTF is an FAU?
    Forced air unit? As in, air handler?

    "There is no exception to the rule that every rule has an exception." -James Thurber, writer and cartoonist (1894-1961)
    www.ArnoldHomeInspections.com

  6. #6
    A.D. Miller's Avatar
    A.D. Miller Guest

    Default Re: Condensate line question

    Quote Originally Posted by John Arnold View Post
    Forced air unit? As in, air handler?
    JA: OIC.


  7. #7
    Ron Bibler's Avatar
    Ron Bibler Guest

    Default Re: Condensate line question

    Quote Originally Posted by A.D. Miller View Post
    JA: OIC.
    Bagdad Bob....I.D.U.E....

    Best

    Ron


  8. #8
    A.D. Miller's Avatar
    A.D. Miller Guest

    Default Re: Condensate line question

    Quote Originally Posted by Ron Bibler View Post
    Bagdad Bob....I.D.U.E....

    Best

    Ron
    RB: IDKTMWIM . . .


  9. #9

    Default Re: Condensate line question

    I wouldn't want 2 units on one condensate drain line, particularly if they are equipped with secondary type shut-offs. One blockage shuts off both units. You could also argue that the manufacturer asks for a 3/4 drain on every unit & although there is nothing that expressly prohibits it, I would not consider it a best or even good practice.

    Clarksville Home Inspection
    JW Goad
    TN License #307 | KY License #2402

  10. #10
    Join Date
    Sep 2008
    Location
    so so, California
    Posts
    1,867

    Default Re: Condensate line question

    Quote Originally Posted by John Goad View Post
    I wouldn't want 2 units on one condensate drain line, particularly if they are equipped with secondary type shut-offs. One blockage shuts off both units. You could also argue that the manufacturer asks for a 3/4 drain on every unit & although there is nothing that expressly prohibits it, I would not consider it a best or even good practice.
    John, I feel the same way, just looking for other opinions. Thanks for the input.


  11. #11
    A.D. Miller's Avatar
    A.D. Miller Guest

    Default Re: Condensate line question

    M1411.3.2 Drain pipe materials and sizes.
    Components of
    the condensate disposal system shall be cast iron, galvanized
    steel, copper, polybutylene, polyethylene, ABS, CPVC or
    PVC pipe or tubing. All components shall be selected for the
    pressure and temperature rating of the installation. Condensate
    waste and drain line size shall be not less than
    3/4-inch (19 mm)
    internal diameter and shall not decrease in size from the drain
    pan connection to the place of condensate disposal. Where the
    drain pipes from more than one unit are manifolded together
    for condensate drainage, the pipe or tubing shall be sized in
    accordance with an approved method. All horizontal sections
    of drain piping shall be installed in uniform alignment at a uniform
    slope.




  12. #12
    Join Date
    Mar 2007
    Location
    Atlanta, Georgia
    Posts
    1,088

    Default Re: Condensate line question

    Seems like we discussed this recently but cannot find it so here goes again...

    The high efficiency forced air gas furnance has a condensate line. The attached A/C has a condensate line. They are both 3/4" PVC properly sloped away from the unit. About 3 feet from the unit, the two pipes join into a single 3/4" pipe.

    The pipes join but do not increase in size. The furance and AC would never be running at the same time so as long as the pipe is adequately sized for a each appliance, then joining them should not make a difference, right???

    Instead of two holes in the foundation wall with two pvc pipes dripping on to the backyard, they used one pipe and saved $3 on the ten foot piece of pvc. It just seems wrong.

    Whadda ya think?

    "The Code is not a peak to reach but a foundation to build from."

  13. #13
    David Bell's Avatar
    David Bell Guest

    Default Re: Condensate line question

    The 2 together are fine, when it is in heating mode they are both trapped to maintain system pressure per manufacturers instructions,, in cooling mode only the coil is drained and seperatly trapped so,,no problem.


  14. #14
    kirk mcloren's Avatar
    kirk mcloren Guest

    Default Re: Condensate line question

    I favor a separate line for each unit. I saw an AC in Palm Desert Ca with a plugged 3/4 condensate drain from a jello like bacterial substance. Carpet around air handler was soaked because the water had no place to go.
    Just when you think you have seen it all.


  15. #15
    Clifford Mark's Avatar
    Clifford Mark Guest

    Default Re: Condensate line question

    Hey guys,

    In Texas we always call an exterior primary condensate drain line installation 'deficient' if not extended at least 36 inches straight out from the foundation. At a recent seminar, a fellow inspector was told this 36" requjirement is not in 'the code.' It seems to be rather common practice to keep moisture out from under the clay-dominated soils we have in many Texas locales. Is it part of the mechanical code, an advisory matter, a common practice thing, a practical recommendation that has become a standard (like common law) or is it just a HI myth?

    Cliff


  16. #16
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: Condensate line question

    Quote Originally Posted by Clifford Mark View Post
    Hey guys,

    In Texas we always call an exterior primary condensate drain line installation 'deficient' if not extended at least 36 inches straight out from the foundation. At a recent seminar, a fellow inspector was told this 36" requirement is not in 'the code.' It seems to be rather common practice to keep moisture out from under the clay-dominated soils we have in many Texas locales. Is it part of the mechanical code, an advisory matter, a common practice thing, a practical recommendation that has become a standard (like common law) or is it just a HI myth?

    Cliff
    Cliff,

    Not in the IRC, it could possibly be like the Florida Building Code, Residential in that the condensate drain line is required to discharge a minimum of 1 foot from the foundation, not because of expansive soils, but because of protection from termites.

    Not sure if Texas has something like that or not, but from past information on codes in Texas, Texas uses the IRC, so the answer would likely be 'No, there is no code requirement for that, but ... there may well be a local requirement or soil engineering requirement for that because of the expansive soil.'

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  17. #17
    Rick Hill's Avatar
    Rick Hill Guest

    Default Re: Condensate line question

    If your FAU's are 90% furnaces your condesate is acidic in winter. You do not want it coming in contact with your cement foundation as it will eat away at it.


  18. #18
    Join Date
    Mar 2007
    Location
    Fuquay Varina, NC
    Posts
    1,074

    Default Re: Condensate line question

    I don't think the water is acidic for it would eat away at the coil. It has metallic properties and will kill the grass. Has anyone ever tested the water ?
    The common practice is to get it away from the foundation because it can produce several gallons a day and saturating the soils at that location causing uneven soil bearing from the dry soil areas. For instance clay would be expanded at that location.

    Mike Schulz License 393
    Affordable Home Inspections
    www.houseinspections.com

  19. #19
    Binford Tools's Avatar
    Binford Tools Guest

    Default Re: Condensate line question

    Quote Originally Posted by Mike Schulz View Post
    I don't think the water is acidic for it would eat away at the coil. It has metallic properties and will kill the grass. Has anyone ever tested the water ?
    The common practice is to get it away from the foundation because it can produce several gallons a day and saturating the soils at that location causing uneven soil bearing from the dry soil areas. For instance clay would be expanded at that location.
    The water coming out the furnace is it is slightly acidic. The water comming off the A/C coils in the summer is not. The code here has changed and they don't want the furnace water in the sewer drain. They like it to go into the flower beds.


  20. #20
    David Bell's Avatar
    David Bell Guest

    Default Re: Condensate line question

    Condensing furnaces typically have a PH of 3.5 to 3.8 which is only slightly more acidic than beer, tho I try not to pour that down the sink either, it is not because I am afraid of rotting anything but my liver. (tongue planted firmly in cheek)

    Last edited by David Bell; 05-06-2011 at 11:33 AM.

Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •