Results 1 to 23 of 23
Thread: Condensate trap too big?
-
06-14-2010, 01:48 PM #1
Condensate trap too big?
This condensate trap for an A/C connection seemed a bit too large but I wasn't sure if it was actually wrong.
Is there a limit to the size?
Similar Threads:
-
06-14-2010, 02:23 PM #2
Re: Condensate trap too big?
Jon,
Ever try and push water uphill?
Yes, its wrong.
rick
-
06-14-2010, 02:23 PM #3
-
06-14-2010, 02:34 PM #4
Re: Condensate trap too big?
And leaking, it appears...
We know why you fly: because the bus is too expensive and the railroad has a dress code...
www.atozinspector.com
-
06-14-2010, 03:00 PM #5
Re: Condensate trap too big?
See attached:
-
06-14-2010, 05:19 PM #6
Re: Condensate trap too big?
Very wrong, but probably works as the coil is probably about 4.5' off the ground.
-
06-17-2010, 03:23 PM #7
-
06-17-2010, 03:52 PM #8
Re: Condensate trap too big?
Ummm, size would appear to be the least of the problems. That's really a beautiful set-up. So do those pipes go down into a crawl? Looks like a great rodent highway.
-
06-17-2010, 09:53 PM #9
Re: Condensate trap too big?
It's all wrong, what it needs is a condensation pump with a drain line that is routed overhead and into the PVC drain pipe.
-
06-18-2010, 03:35 AM #10
Re: Condensate trap too big?
I tend to disagree with this "quick Fix". My experience with condensation pumps is that it's another point of failure. They tend to quit a lot, and its usually an item that may be looked at one a year if you are lucky. This should be a last resort if a good condensation gravity system can't be installed.
-
06-18-2010, 06:08 AM #11
Re: Condensate trap too big?
Besides the length of the drain 'trap"; Isn't a condensate trap supposed to have an air gap(?) and not be directly connected to the sanitary sewer?
-
06-18-2010, 08:42 AM #12
-
06-18-2010, 09:39 AM #13
-
06-18-2010, 09:45 AM #14
Re: Condensate trap too big?
you're right, my fault...
-
06-18-2010, 10:09 AM #15
-
06-18-2010, 10:16 AM #16
-
06-18-2010, 10:18 AM #17
Re: Condensate trap too big?
seeing as there is no potable water connection at the heater, I'd say that'd be a no....
But sewage backflow...even if it were just gases...wouldn't be a nice scene in the air flow of the unit.
-
06-18-2010, 12:37 PM #18
Re: Condensate trap too big?
The requirement for condensate is much the same as effluent, trapped at the closest place and subject to venting requirements.
-
06-18-2010, 01:27 PM #19
Re: Condensate trap too big?
Where is the specification that the horizontal piece of a trap cannot be 6"...12" or even 96" on a condensate line.
I looked at the links provided and all that was specified was height requirements. Nothing about from one vertical to the other.
Please educate me.
-
06-19-2010, 05:50 PM #20
Re: Condensate trap too big?
The condensate piping by itself is only subject to condensate guidlines. But once you connect that to a homes DWV system, it must adhere to all codes and regulations that all piping in that system conforms to.
-
06-21-2010, 09:15 AM #21
Re: Condensate trap too big?
Okay....so you are saying what?
-
06-21-2010, 03:40 PM #22
-
11-20-2011, 03:45 PM #23
Re: Condensate trap too big?
WRT the necessity of traps on the suction side of air handlers, this may be of interest:
Condensation in ceiling - Contractor Talk HVAC forum
Bookmarks