Results 1 to 7 of 7
  1. #1
    mathew stouffer's Avatar
    mathew stouffer Guest

    Default Slope of furnace vent

    Garage furnace with an induced draft vent. It is allowed to slope downward? Could not find any installation instructions. Place was built in 07

    Similar Threads:
    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    Crawl Space Creeper

  2. #2
    Join Date
    Mar 2007
    Location
    Spring City/Surrounding Philadelphia area
    Posts
    3,509

    Default Re: Slope of furnace vent

    I don't see those types of units around here.

    Is that a condensate stain on the plate beneath the flue pipe?

    "It takes a big man to cry. It takes an even bigger man to laugh at that man". - Jack Handey

  3. #3
    Join Date
    Mar 2007
    Location
    Philadelphia PA
    Posts
    3,177

    Default Re: Slope of furnace vent

    No way.
    The Simpson Dura-Vent instructions I have say that any "horizontal" sections must slope upwards away from the appliance at least 1/4" per foot. I don't think it would say that if you were allowed to vent vertical sections down as shown.

    "There is no exception to the rule that every rule has an exception." -James Thurber, writer and cartoonist (1894-1961)
    www.ArnoldHomeInspections.com

  4. #4
    Join Date
    Mar 2007
    Location
    Santa Rosa, CA
    Posts
    3,154

    Default Re: Slope of furnace vent

    Induced draft is still considered natural draft and must be installed as such. As John said, needs correct slope.

    Department of Redundancy Department
    Supreme Emperor of Hyperbole
    http://www.FullCircleInspect.com/

  5. #5
    Join Date
    Jul 2008
    Location
    Utah
    Posts
    390

    Thumbs down Re: Slope of furnace vent

    Agreed as flat out wrong.


  6. #6
    David Bell's Avatar
    David Bell Guest

    Default Re: Slope of furnace vent

    Also, clearance from venting to gas pipe not good, no sediment trap on gas line, clearance of unit to ceiling could be suspect.


  7. #7
    Scott Craig's Avatar
    Scott Craig Guest

    Default Re: Slope of furnace vent

    Quote Originally Posted by mathew stouffer View Post
    Garage furnace with an induced draft vent. It is allowed to slope downward? Could not find any installation instructions. Place was built in 07
    Must admit, I have never seen a set up like that! But really looks wrong. Don't think it should ever slope down!


Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •