    Default Venting a high efficient system

    This is a 6 year old Ruud 120,000 btu gas forced air system. I'm looking for documentation why the venting pipe diameter should not be reduced. There was no manual with this unit and I cannot find anything from the manufacturer.

    Similar Threads:
    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    Member Benefits1

  2. #2
    David Bell's Avatar
    David Bell Guest

    Default Re: Venting a high efficient system

    It can leave the furnace at 2" and increase to 3" but increasing on a horizontal run requires eccentric reducers to facilitate proper condensate flow back to the furnace.

    Last edited by David Bell; 12-25-2010 at 09:59 AM.

  3. #3
    Join Date
    Feb 2008
    Location
    Chicago IL
    Posts
    2,048

    Default Re: Venting a high efficient system

    I would suggest going to the Rheem/Ruud website and pulling pdf's off of there. Typically from my experience, anything over 100K is specified with 3" PVC.

    www.aic-chicago.com
    773/844-4AIC