Thread: Venting a high efficient system
-
12-24-2010, 11:37 AM #1
Venting a high efficient system
This is a 6 year old Ruud 120,000 btu gas forced air system. I'm looking for documentation why the venting pipe diameter should not be reduced. There was no manual with this unit and I cannot find anything from the manufacturer.
Similar Threads:
-
12-24-2010, 03:24 PM #2
Re: Venting a high efficient system
It can leave the furnace at 2" and increase to 3" but increasing on a horizontal run requires eccentric reducers to facilitate proper condensate flow back to the furnace.
Last edited by David Bell; 12-25-2010 at 09:59 AM.
-
12-24-2010, 05:39 PM #3
Re: Venting a high efficient system
I would suggest going to the Rheem/Ruud website and pulling pdf's off of there. Typically from my experience, anything over 100K is specified with 3" PVC.