    I came across the application of a window type AC system yesterday installed at a interior garage wall for a converted interior garage bedroom and am looking for verbiage to use in describing potential problems....

    Similar Threads:
    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    Crawl Space Creeper

  2. #2
    Join Date
    Mar 2007
    Location
    Plano, Texas
    Posts
    4,245

    Default Re: Unusual AC installation

    The biggest issue is carbon monoxide intrusion through the breach in the separation wall between the garage and house. Easy fix, take it out and restore the wall.
    Then there are other issues with condensation and excess heat pumped into the garage.

    Jim Luttrall
    www.MrInspector.net
    Plano, Texas