Goodman condenser overcurrent protection
Damaged label on Goodman condenser at new construction inspection. Appears to be 4-ton unit.
Anyone know what the max overcurrent protection should be? There is a 40 amp circuit breaker in the panel, which may be correct, but I wouldn't be surprised if it was a tad too big.
Similar Threads:"There is no exception to the rule that every rule has an exception." -James Thurber, writer and cartoonist (1894-1961)
www.ArnoldHomeInspections.com
-
11-01-2012, 04:10 AM #2
Re: Goodman condenser overcurrent protection
Max OCD is 45 according to Goodman.
See it here page 6:
-