    Default Goodman condenser overcurrent protection

    Damaged label on Goodman condenser at new construction inspection. Appears to be 4-ton unit.
    Anyone know what the max overcurrent protection should be? There is a 40 amp circuit breaker in the panel, which may be correct, but I wouldn't be surprised if it was a tad too big.

    Similar Threads:
    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    OREP Insurance
    "There is no exception to the rule that every rule has an exception." -James Thurber, writer and cartoonist (1894-1961)
    www.ArnoldHomeInspections.com

  2. #2
    Join Date
    Mar 2007
    Location
    Orlando, FL
    Posts
    1,594

    Default Re: Goodman condenser overcurrent protection

    Max OCD is 45 according to Goodman.

    See it here page 6:

    Attached Files Attached Files

  3. #3
    Join Date
    Mar 2007
    Location
    Philadelphia PA
    Posts
    3,177

    Default Re: Goodman condenser overcurrent protection

    Quote Originally Posted by Dom D'Agostino View Post
    Max OCD is 45 according to Goodman.

    See it here page 6:
    Thanks!