Results 1 to 6 of 6
  1. #1
    Join Date
    Mar 2007
    Location
    New Mexico
    Posts
    1,352

    Default Boiler Circulation Pump

    Did something change in our electrical / mechanical codes requiring protection for the cable to the boiler circulating pump? I've seen this 3 times in the past few weeks, where I would normally see type MC cable.

    Similar Threads:
    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    Member Benefits1
    Jim Robinson
    New Mexico, USA

  2. #2
    Join Date
    Mar 2007
    Location
    New Mexico
    Posts
    1,352

    Default Re: Boiler Circulation Pump

    I saw another one today. Anyone have an idea? I don't mind calling out stuff even if it's just a good idea, but I hate to look like a clown if the electrician comes back to me.

    Jim Robinson
    New Mexico, USA

  3. #3
    Join Date
    Feb 2008
    Location
    Caledon, Ontario
    Posts
    4,982

    Default Re: Boiler Circulation Pump

    Jim

    It all depends on what the manufacture instructions/manual require.

    However I did see what appears to be a kink/cut/damage on the cord just done from the motor.


  4. #4
    Join Date
    Dec 2009
    Location
    Florida
    Posts
    553

    Default Re: Boiler Circulation Pump

    I had an experience where a oil-fired furnace and a oil-fired HW heater where each had a loop of Romex instead of MC. When I questioned the local inspector he said that protection was not required as it was only a residence and not a commercial installation. Go figure. Was there any inspection performed on the installations?


  5. #5
    Join Date
    Jul 2010
    Location
    Wisconsin
    Posts
    274

    Default Re: Boiler Circulation Pump

    That looks like UF and under the 2011 NEC Art. 340, UF is installed as nonmetallic-sheathed cable. IMO, you could not wire it this way per the NEC, no protection from damage, looks like it just hangs down unsecured, does not follow any building structure, and just looks like sloppy work.



  6. #6
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: Boiler Circulation Pump

    Quote Originally Posted by Mike Kleisch View Post
    That looks like UF and under the 2011 NEC Art. 340, UF is installed as nonmetallic-sheathed cable. IMO, you could not wire it this way per the NEC, no protection from damage, looks like it just hangs down unsecured, does not follow any building structure, and just looks like sloppy work.
    I think that is an "appliance cord", whether or not it is approved for installation on that pump (the pump would need to be listed for cord and plug installation) is not known - some of those pumps are, others are not.

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •