02-17-2016, 10:27 AM #1
HVAC DISCONNECT SWITCH. SEE PHOTOS
Two consecutive new construction homes in a row, both without a readily accessible and visible HVAC disconnect switch near the equipment (attic unit). See the two photos and you can see the yellow Romex AC line goes from the unit and routes overhead and then disappears downward into the insulation below. I followed every inch and no service disconnect switch in the attic. This is two new house in a row, but different towns and different builders. I don't think there has been a change requiring a service disconnect but I am just double checking since two houses in a row were like this. See the photos.
Similar Threads:
-
02-17-2016, 06:05 PM #2
Re: HVAC DISCONNECT SWITCH. SEE PHOTOS
The absence of a power disconnect warrants a comment in my reports simply from the standpoint of a good practice. Therefore whether or not there's a requirement is irrelevant to me.
Eric Barker, ACI
Lake Barrington, IL
-
02-17-2016, 06:25 PM #3
Re: HVAC DISCONNECT SWITCH. SEE PHOTOS
Robert Young's Montreal Home Inspection Services Inc.
Call (514) 489-1887 or (514) 441-3732
Our Motto; Putting information where you need it most, "In your hands.”
-
02-17-2016, 07:03 PM #4
-
02-17-2016, 07:14 PM #5
Re: HVAC DISCONNECT SWITCH. SEE PHOTOS
hvac.JPG
Looks like a leak, but from what?
Robert Young's Montreal Home Inspection Services Inc.
Call (514) 489-1887 or (514) 441-3732
Our Motto; Putting information where you need it most, "In your hands.”
-
02-17-2016, 07:26 PM #6
Re: HVAC DISCONNECT SWITCH. SEE PHOTOS
That lock out for the air handler unit is not permitted as the code requires the disconnect to in, on or within sight of (the 50 foot straight-line sight rule) "air-conditioning or refrigeration equipment", which includes air handlers.
And when the disconnect is in or on the equipment, it is not allowed to be on a panel removable for service or to block the nameplate labels.
-
02-17-2016, 07:31 PM #7
Re: HVAC DISCONNECT SWITCH. SEE PHOTOS
Thanks Jerry
-
02-18-2016, 03:59 AM #8
Re: HVAC DISCONNECT SWITCH. SEE PHOTOS
I inspected a home last week with two condensers an air handler in the attic and a boiler in the basement and not one had a disconnect near the units. Of course the owner built it.
-
02-18-2016, 05:02 AM #9
Re: HVAC DISCONNECT SWITCH. SEE PHOTOS
Jerry, as usual, your the King Mate!