    Default Air handler installed upside down

    Trane updraft air handler installed upside down......never seen this before. Is there a problem with this installation other than no trap at condensate?

    Sidney Alstad

    Similar Threads:
    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    OREP Insurance

  2. #2
    Join Date
    Feb 2008
    Location
    Caledon, Ontario
    Posts
    4,982

    Default Re: Air handler installed upside down

    I think this may be the model.

    Installers Guide 1-1/2 - 5 Ton Convertible Air ... - Trane
    https://www.google.ca/url?sa=t&rct=j...15339255,d.amc

    Section 7. Setting the Unit - Vertical Installation................................. 18


  3. #3
    Join Date
    Feb 2008
    Location
    Chicago IL
    Posts
    2,048

    Default Re: Air handler installed upside down

    Unless they re-oriented the A coil that could be a real problem. They probably did but did they do a good enough job to keep water from hitting the electronics?
    Beyond that where does that condensate drain hose terminate to, is there an air gap or trap? Are they potentially contaminating the air stream with sewer gases?

    www.aic-chicago.com
    773/844-4AIC
    "The Code is not a ceiling to reach but a floor to work up from"

  4. #4
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,032

    Default Re: Air handler installed upside down

    As Marcus was headed (I think) - vertically and right side up is not the same as vertically and up side down.

    I may have missed it looking on my phone, but I didn't see anything permitting vertically and up side down, regardless of any changes made.

    As Marcus pointed out up ... vertically and up side down puts any and all condensation above the electronics ... which I doubt is approved by the manufacturer.

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  5. #5
    Join Date
    Jul 2010
    Location
    NC
    Posts
    122

    Default Re: Air handler installed upside down

    Quote Originally Posted by Markus Keller View Post
    Unless they re-oriented the A coil that could be a real problem. They probably did but did they do a good enough job to keep water from hitting the electronics?
    Beyond that where does that condensate drain hose terminate to, is there an air gap or trap? Are they potentially contaminating the air stream with sewer gases?
    Crawlspace was not entered due to 3-6" of standing water and mud inside of crawlspace of this modular home, so I do not know where the condensate terminates. If the crawl was accessible, it is it is doubtful anything would be visible as sheathing is adhered to floor framing members, all that was visible from hatch was the steel rails and sheathing.


  6. #6
    Join Date
    Feb 2008
    Location
    Caledon, Ontario
    Posts
    4,982

    Default Re: Air handler installed upside down

    If in the picture this is the same unit as a Trane TEM4 Air Handler its rated for Multi-Position Installation.

    Trane TEM4 Air Handler | High Quality Heating & Air, Inc.


  7. #7
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,032

    Default Re: Air handler installed upside down

    There is still a right side up and up side down to mult - position and convertible horizontal/vertical units.

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  8. #8
    Join Date
    Feb 2008
    Location
    Caledon, Ontario
    Posts
    4,982

    Default Re: Air handler installed upside down