Results 1 to 16 of 16
  1. #1
    Join Date
    Sep 2008
    Location
    so so, California
    Posts
    1,867

    Default Is the clearance rule 10 feet here?

    Last edited by Marc M; 01-18-2010 at 09:04 PM.
    OREP Insurance

  2. #2
    Join Date
    Oct 2003
    Location
    Rockwall Texas
    Posts
    4,521

    Default Re: Is the clearance rule 10 feet here?

    Is that a "swamp" cooler?


  3. #3
    Join Date
    Sep 2008
    Location
    so so, California
    Posts
    1,867

    Default Re: Is the clearance rule 10 feet here?

    Indeed it is.


  4. #4
    Join Date
    Mar 2007
    Location
    Ridgewood, NJ
    Posts
    237

    Default Re: Is the clearance rule 10 feet here?

    B vent manufacturer Hart & Cooley installation instructions say 8 foot clearance reqired to a vertical wall. If the there is less than the 8 feet clearance, the vent must be raised 2 feet above the structure.

    I don't know, does that qualify as a wall or structure?


  5. #5
    Join Date
    Mar 2007
    Location
    New Mexico
    Posts
    1,352

    Default Re: Is the clearance rule 10 feet here?

    That is a major air intake for the house, and you definitely don't want that vent located right next to it like that.

    Jim Robinson
    New Mexico, USA

  6. #6
    Join Date
    Mar 2007
    Location
    Ridgewood, NJ
    Posts
    237

    Default Re: Is the clearance rule 10 feet here?

    Jim, It's an air conditioning unit, not a "major air intake".


  7. #7
    Join Date
    Mar 2007
    Location
    Plano, Texas
    Posts
    4,245

    Default Re: Is the clearance rule 10 feet here?

    Quote Originally Posted by neal lewis View Post
    Jim, It's an air conditioning unit, not a "major air intake".
    Yep, it is a MAJOR fresh air intake, NOT an air conditioning unit.
    Swamp cooler = evaporative cooler, not a refrigerated air unit.
    You won't see these in more humid parts of the country, since it adds humidity to the air in order to lower the temperature.
    The louvered panels you see in the picture are air inlet grills that usually have a wet straw mat behind it. Air is drawn through the mat and directly into the house displacing the warm air with cooler air.
    Right, Jim (the other Jim )

    Jim Luttrall
    www.MrInspector.net
    Plano, Texas

  8. #8
    Join Date
    Mar 2007
    Location
    Plano, Texas
    Posts
    4,245

    Default Re: Is the clearance rule 10 feet here?

    Try this for size.
    Welcome To Home Energy Magazine Online

    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    Jim Luttrall
    www.MrInspector.net
    Plano, Texas

  9. #9
    Join Date
    Mar 2007
    Location
    New Mexico
    Posts
    1,352

    Default Re: Is the clearance rule 10 feet here?

    It's a southwest thing. They are all over out here, not so much in NJ.

    Jim Robinson
    New Mexico, USA

  10. #10
    Join Date
    Sep 2008
    Location
    so so, California
    Posts
    1,867

    Default Re: Is the clearance rule 10 feet here?

    Yea...EVERYTHING is weird in california!


  11. #11
    Join Date
    Mar 2007
    Location
    Columbus GA
    Posts
    3,747

    Default Re: Is the clearance rule 10 feet here?

    What kink of crazy world do you all live in; making the air MOVE humid.What happened to my smiley face?

    ' correct a wise man and you gain a friend... correct a fool and he'll bloody your nose'.

  12. #12
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: Is the clearance rule 10 feet here?

    Swamp Cooler (never seen one myself, but heard of them).

    Is that why there is a hose bibb there?

    Two things:

    1) Yes, *I* would treat that as a "wall" next to the B vent, meaning it needs to be 8 feet away or 2 feet above it.

    2) Being as that is a "swamp cooler", get it away from the air intake.

    Nothing is flashed properly there either.

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  13. #13
    Join Date
    Sep 2008
    Location
    so so, California
    Posts
    1,867

    Default Re: Is the clearance rule 10 feet here?

    Thats funny. Jerry, you make it sound like big foot. But I suppose you wouldnt have ever seen one in FLA, no shortage of humidity there.


  14. #14
    Join Date
    Mar 2007
    Location
    Plano, Texas
    Posts
    4,245

    Default Re: Is the clearance rule 10 feet here?

    Quote Originally Posted by Rick Cantrell View Post
    What kink of crazy world do you all live in; making the air MOVE humid.What happened to my smiley face?
    My thoughts exactly concerning humidifiers installed up north (actually people from up north installing them in houses down south)

    Jim Luttrall
    www.MrInspector.net
    Plano, Texas

  15. #15
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: Is the clearance rule 10 feet here?

    Quote Originally Posted by Marc M View Post
    Thats funny. Jerry, you make it sound like big foot.
    Marc,

    No, ... I saw ... big foot once ...

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  16. #16
    Join Date
    Mar 2007
    Location
    Near Philly, Pa.
    Posts
    1,682

    Talking Re: Is the clearance rule 10 feet here?

    B-vent would need to be 2 ft taller than the Swamp Thing and it needs a storm collar. While they're at it, they can remove all that combustible plastic roof cement from the B-vent.

    Keep the fire in the fireplace.

Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •