You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!
If you have any problems with the registration process or your account login, please contact us.
Why join InspectionNews? Read the Testimonials
|
|

05-22-2007, 05:46 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 746
|
|
|
Wall heater register
Just wanted to double check on this one.
A wall heater in the living room. The bedroom is on the other side of this wall (pic #1). A register/vent has been installed in the bedroom (pic #2). Someone cut through the wall and the backside of the wall heater (pic #3). I am writing that the heater has been modified and advising replacement, but wanted to make sure.
__________________
The apostrophe troll.
|
|

05-24-2007, 12:01 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Austin, TX
Posts: 282
|
|
|
Re: Wall heater register
Gunnar,
It's hard to tell from the 3rd photo, but did they just cut out the back of the heater to make the vent?
Eric
|
|

05-24-2007, 12:28 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Columbus GA
Posts: 382
|
|
|
Re: Wall heater register
Gunnar
Without knowing if the modifications were approved (or even designed by the manufacturer) you might hold off on recommending replacement. Instead you could say something like, the wall furnace looks like it has been modified ( addition of a vent to the bedroom), it is beyond the scope of this inspection to determine if the modification violates the manufacturers installation requirements. Recommend you have a certified/ licensed heating contractor that is familiar with this type of heating system to determine if the modification will affect its safety.
__________________
Rick Cantrell
Columbus GA
|
|

05-24-2007, 06:03 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 746
|
|
|
Re: Wall heater register
Eric,
Looked like it was cut open with tin snips.
Rick,
You might be right, but it seems to me that this essentially puts the heater in the bedroom. (UMC 904.5). As far as I know, open flame heating appliances are not allowed in bedrooms.
However, it doesn't really matter now. The report went out a couple of days ago.
__________________
The apostrophe troll.
|
|

05-24-2007, 09:10 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Duncanville, Tx
Posts: 1,086
|
|
|
Re: Wall heater register
Gunnar is right. It does essentially put the furnace in the bedroom.
I do alot of these old type set ups in Oak Cliff (very old section of Dallas) and most of these old wall-mounted heaters really are to the point of needing replacing because of the potential fire hazard. I've never seen one that I'd want to keep in the home for my family.
Rich.
__________________
"If con is the opposite of pro, is Congress the opposite of progress?"
Richard Rushing, HCRI
Duncanville, Tx.
|
|

05-24-2007, 10:37 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Corpus Christi, TX
Posts: 582
|
|
|
Re: Wall heater register
R.R.
They are approved for mother-in-law apartments. 
__________________
The only reason some people get lost in thought is because it's unfamiliar territory.
- Paul Fix
|
|

05-25-2007, 07:58 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: San Diego, CA
Posts: 74
|
|
|
Re: Wall heater register
Wall furnaces are allowed in sleeping rooms, as long as the sleeping room is large enough to be considered unconfined space.
|
|

05-25-2007, 09:20 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: San Mateo, CA
Posts: 1,103
|
|
|
Re: Wall heater register
2006 IRC - M1409.3 Installation: Vented wall furnace installations shall conform to the following requirements:
1. Required wall thicknesses shall be in accordance with the manufacturer’s installation instructions.
2. Ducts shall not be attached to a wall furnace. Casing extensions or boots shall be installed only when listed as part of a listed and labeled appliance.
3. A manual shut off valve shall be installed ahead of all controls.
Note item #2.
|
|
| Thread Tools |
Search this Thread |
|
|
|
Posting Rules
|
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts
HTML code is Off
|
|
|
| Thread |
Thread Starter |
Forum |
Replies |
Last Post |
| Wall temperature |
Vince Santos |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
23 |
05-11-2007 02:07 PM |
| wall/floor cracks |
Vince Santos |
Structural Components: Home Inspection and Commercial Inspection |
2 |
05-07-2007 08:43 AM |
| Black stuff on a wall. |
K Robertson |
Environmental, Pests, Health and Safety: Home Inspection and Commercial Inspection |
7 |
05-01-2007 03:18 PM |
| Crack in the wall |
Mike Huppi |
Building Interior: Home Inspection and Commercial Inspection |
17 |
04-18-2007 12:44 PM |
| Owners must prepare for injury - Orange County Register |
Brian Hannigan |
Business Operations: Home Inspectors & Commercial Inspectors |
0 |
03-26-2007 06:40 PM |
All times are GMT -7. The time now is 11:09 AM.
| | |
|