You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack (1) Thread Tools Search this Thread
  1 links from elsewhere to this Post. Click to view. #1 (permalink)  
Old 06-09-2007, 08:15 AM
dan orourke dan orourke is offline
Member
 
Join Date: Mar 2007
Location: dust in the wind
Posts: 157
P-trap on wrong side of vent
...............

Last edited by dan orourke : 01-02-2008 at 09:01 AM.
Reply With Quote
Home inspection
  #2 (permalink)  
Old 06-09-2007, 09:36 AM
Scott Patterson's Avatar
Scott Patterson Scott Patterson is offline
Member
 
Join Date: Mar 2007
Location: Spring Hill (Nashville), TN
Posts: 1,751
Re: P-trap on wrong side of vent
Quote:
Originally Posted by Brett Foster View Post
Another inspector myth....it can be on either side.
Nope, you are incorrect. The main goal of the trap is to keep from sucking air into the evaporator unit. If it is before the trap, it will suck air into the unit. The trap keeps air from entering the unit, so you want any vent after the trap.

Dan, I don't believe this is in the codes. I have only seen it in the manufacturers requirements. This is not to say the some AHJ's might have a different take on it.
__________________
Scott Patterson
Spring Hill, TN
http://www.traceinspections.com

Last edited by Scott Patterson : 06-09-2007 at 09:44 AM.
Reply With Quote
  #3 (permalink)  
Old 06-09-2007, 12:10 PM
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,644
Re: P-trap on wrong side of vent
Dan,

That does not 'cause' a running trap, a "running trap" is a trap where the inlet and outlet are approximately the same elevation, i.e., you have a pipe and bend the pipe down and back up to the original level.

A "trap" for an a/c unit has the inlet higher than the outlet, typically at least 2" higher.

Otherwise, all you have is a 'bent piece of pipe'.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
Reply With Quote
  #4 (permalink)  
Old 06-09-2007, 12:24 PM
Thom Walker's Avatar
Thom Walker Thom Walker is offline
Member
 
Join Date: Mar 2007
Location: Corpus Christi, TX
Posts: 582
Re: P-trap on wrong side of vent
Quote:
Originally Posted by Brett Foster View Post
Another inspector myth....it can be on either side.
Brett,
Your running theme seems to be Inspector Myths. May I assume you are not an Inspector? None-the-less:

In the future, instead of just spouting Rhetoric, how about some meaningful backup? Otherwise, you sound like just another guy who got pissed off because some inspector cost you money when you had to fix what you were paid to do correctly the first time.

We have plenty of non inspectors on this board and always welcome more. Nobody here has a problem with being proved "wrong". The object is to be better, not right in our first opinions.

And please do fill in your profile.
__________________
The only reason some people get lost in thought is because it's unfamiliar territory.
- Paul Fix

Last edited by Thom Walker : 06-09-2007 at 12:26 PM. Reason: grammar
Reply With Quote
  #5 (permalink)  
Old 06-09-2007, 05:47 PM
DavidR's Avatar
DavidR DavidR is offline
Member
 
Join Date: May 2007
Location: Frankfort, KY
Posts: 176
Re: P-trap on wrong side of vent
In those pictures posted the trap is serving no useful purpose as it is being bypassed.

Best thing to do in that situation is recommend a cap be placed over the existing pipe & cut a tee in on the outlet side of the trap with a standpipe for a vent.
__________________
Measured Performance more than just a buzzword
Reply With Quote
  #6 (permalink)  
Old 06-10-2007, 05:53 AM
David R2 David R2 is offline
Member
 
Join Date: Jun 2007
Location: cold climate
Posts: 16
P trap is first in line.
the trap has to be the first thing that water flows through before it enters the rest of the plumbing system. Vents are in the plumbing system, to help water flow once it enters, after the P trap.

Standpipes are a way to enable high flow drains like washing machines to put their water out first and not fight against resistance from a P trap. They are like temporary holding tanks. Not applicable here.

David
Reply With Quote
  #7 (permalink)  
Old 06-10-2007, 02:14 PM
DavidR's Avatar
DavidR DavidR is offline
Member
 
Join Date: May 2007
Location: Frankfort, KY
Posts: 176
Re: P-trap on wrong side of vent
I think I will continue to put the standpipes in.

Last time I placed a straw in a full glass of water & pulled that straw out with my finger on top the water didn't flow out of the straw till I removed my finger.

I want as little resistance on that drain as possible while the fan is running if it is on the return side of the fan.
__________________
Measured Performance more than just a buzzword
Reply With Quote
Home inspection
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On

LinkBacks (?)
LinkBack to this Thread: http://www.inspectionnews.net/home_inspection/heating-ventilation-air-conditioning-hvac-home-inspection-commercial-inspection/1566-p-trap-wrong-side-vent.html
Posted By For Type Date
hvac: Blogs, Photos, Videos and more on Technorati This thread Refback 06-09-2007 10:00 PM

Similar Threads
Thread Thread Starter Forum Replies Last Post
Double p-trap? John Stephenson Plumbing System: Home Inspection and Commercial Inspection 8 06-11-2007 09:39 PM
What's wrong with this vent dan orourke Plumbing System: Home Inspection and Commercial Inspection 3 06-02-2007 08:30 PM
p-trap John Stephenson Plumbing System: Home Inspection and Commercial Inspection 7 05-16-2007 05:28 PM
trap wayne soper Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 4 05-06-2007 01:11 PM
2 Wire Load Side Fuse Panel Michael Thomas Electrical Systems: Home Inspection and Commercial Inspection 2 04-12-2007 03:22 PM


All times are GMT -7. The time now is 11:34 AM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger