Marc,
I am not familiar with the model number of the furnace. But as long as the horizontal portion is sloped at 2% plus (up) and the length is less than 75% of the vertical rise portion, you are ok.
In fact as I recall if the horizontal portion of the vent is insulated it can be up to 100% of the vertical portion.
Someone better help me with that last part, I pulled it from memory and mine has slipped from time to time.
HTH