InspectionNews - Home Inspection


Share |

Welcome to InspectionNews.

Registration is FREE!

Why join InspectionNews? Read the Testimonials

You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but you will not see any of the pictures or technical bulletins that have been uploaded.

There are over 11,850 inspectors who have already joined InspectionNews, contributing over 100,700 posts. By joining InspectionNews you will be able to see the pictures, start new threads, reply to posts, communicate privately with other members, respond to polls, upload content and access many other special features.

If you are an inspector or thinking about becoming one, InspectionNews is the place for you.

Registration is FREE because the sponsors pay your way.
Please visit all the sponsors often and let them know that you found them on InspectionNews!

How much should an inspection cost? Click the banner below to find out.
The Cost Of Business

If you have any problems with the registration process or your account login, please contact us.

Registration is easy, so please Join InspectionNews Today!

Cost Of Business
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 03-17-2010, 08:12 AM
Matthew Barnicle Matthew Barnicle is offline
Member
 
Join Date: Mar 2007
Location: Tampa, Fl
Posts: 150
Romex through Furnace cabinet.
Furnace was installed with romex running in one end, through the furnace cabinet and enters the junction box/connection point on the other side. At best, I am thinking best practice would be to bring it in on the side of the junction box. But is this allowed?
Attached Images
File Type: jpg 104_2918.jpg (55.3 KB, 61 views)
Reply With Quote
FREA Home Inspector Insurance
  #2 (permalink)  
Old 03-17-2010, 08:47 AM
Scott Patterson's Avatar
Scott Patterson Scott Patterson is offline
Member
 
Join Date: Mar 2007
Location: Spring Hill (Nashville), TN
Posts: 3,577
Re: Romex through Furnace cabinet.
Not having the wiring diagram for that unit, I would have to say it is wrong based on common sense! The area that the NM cable is around might get pretty darn warm and I don't think it is rated for the heat that will be in that area. They really had to work hard to do it that way!

Is that flex vent pipe rated for use on this type of unit?
__________________
Scott Patterson
Spring Hill, TN
http://www.traceinspections.com
Reply With Quote
  #3 (permalink)  
Old 03-17-2010, 08:53 AM
Rick Cantrell Rick Cantrell is offline
Member
 
Join Date: Mar 2007
Location: Columbus GA
Posts: 1,352
Re: Romex through Furnace cabinet.
I don't think that running the cable like that is a problem.
I do see a problem with the unit sitting on the pan. If (when) the pan fills with water, the water will be inside the unit.
__________________
' correct a wise man and you gain a friend... correct a fool and he'll bloody your nose'.
Reply With Quote
  #4 (permalink)  
Old 03-17-2010, 08:59 AM
Matthew Barnicle Matthew Barnicle is offline
Member
 
Join Date: Mar 2007
Location: Tampa, Fl
Posts: 150
Re: Romex through Furnace cabinet.
Hi Rick,

It is actually up past the flood rim of the pan, you just cant tell from the photo. The furnace across from this one had a reversed pitch flue, so I called them both out for review with special attention to the romex. I am leaning towards improper install. Otherwise, installers could take liberty and run the romex wherever they pleased in the cabinet. There are clearly some areas in that cabinet that installer wiring should stay away from.
Reply With Quote
  #5 (permalink)  
Old 03-17-2010, 11:59 AM
ray jackson ray jackson is offline
Member
 
Join Date: Dec 2009
Location: bakersfield
Posts: 20
Re: Romex through Furnace cabinet.
Most manufacturers have provisions for the junction box to be moved to either side for this exact reason. All the wiring within the cabinet has been factory tested to function in that state. The installers romex was not present for those tests.
Reply With Quote
  #6 (permalink)  
Old 03-22-2010, 08:16 PM
Phil Narron Phil Narron is offline
Member
 
Join Date: Feb 2010
Location: georgia
Posts: 2
Re: Romex through Furnace cabinet.
Are not all holes supposed to be sealed and the wires coming out of it have a garment too?
Reply With Quote
  #7 (permalink)  
Old 03-23-2010, 05:45 AM
David Bell David Bell is offline
Member
 
Join Date: Oct 2009
Location: CT shoreline
Posts: 509
Re: Romex through Furnace cabinet.
The only holes on this unit that need to be sealed are on the blower compartment, where the low voltage wires enter. The burner compartment does not need to be sealed as combustion air is drawn in through any openings. The romex, while not beautiful, is ok.
Reply With Quote
F.I.R.E. provides fireplace education, consulting services, fire investigation and litigation support across the United States.
Cost Of Business
Reply

Share |

Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
NM romex brianmiller Electrical Systems: Home Inspection and Commercial Inspection 13 02-26-2010 10:08 AM
Yellow Romex Outside? Matt Fellman Electrical Systems: Home Inspection and Commercial Inspection 18 05-22-2009 10:26 AM
Romex through sheetrock? Robert Autrey Electrical Systems: Home Inspection and Commercial Inspection 77 05-17-2009 05:08 PM
Gas supply shut-off valve in furnace cabinet Larry Coha Fireplaces, Chimneys and Solid Fuel Burning Appliances: Home Inspection and Commercial Inspection 10 04-07-2009 08:33 AM
Romex cable mathew stouffer Electrical Systems: Home Inspection and Commercial Inspection 53 08-27-2008 07:14 PM

Alabama | Alaska | Arizona | Atlanta | Aurora | Austin | Baltimore | Boston | California | Cambridge | Cape Coral | Chandler | Charlotte | Chicago | Cincinnati | Clarksville | Cleveland | Colorado | Columbus | Connecticut | Dallas | Delaware | Denver | Detroit | Durham | El Paso | Eugene | Florida | Fort Worth | Fresno | Georgia | Gilbert | Hawaii | Henderson | Houston | Huntsville | Idaho | Illinois | Indiana | Indianapolis | Irvine | Jacksonville | Joliet | Kansas City | Knoxville | Lancaster | Las Vegas | Los Angeles | Louisiana | Louisville | Maine | Maryland | Massachusetts | Memphis | Mesa | Miami | Michigan | Milwaukee | Minneapolis | Minnesota | Miramar | Mississippi | Missouri | Montana | Nashville | Nebraska | Nevada | New Hampshire | New Jersey | New Mexico | New York | North Carolina | North Dakota | Oakland | Ohio | Oklahoma | Omaha | Ontario | Orange | Oregon | Orlando | Pennsylvania | Philadelphia | Phoenix | Pittsburgh | Plano | Portland | Port StLucie | Raleigh | Rhode Island | Roseville | Sacramento | Salem | San Antonio | San Diego | San Francisco | San Jose | Scottsdale | Seattle | Sioux falls | South Carolina | South Dakota | St Louis | Tampa | Tennessee | Texas | Thornton | Toledo | Tucson | Tulsa | Utah | Vancouver | Vermont | Virginia | West Virginia | Wichita | Wisconsin | Wyoming | Cost To Repair

All times are GMT -7. The time now is 08:31 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2010, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger