You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!
If you have any problems with the registration process or your account login, please contact us.
Why join InspectionNews? Read the Testimonials
|
|

08-18-2007, 09:46 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Highland, IN
Posts: 369
|
|
|
Clearance for an air conditioner
I'm wondering if there have been any carrier unit that allow under 24 inch clearance from top of unit. My thinking is no. I did a search but no luck on Carrier units.
__________________
I say lets merge all the home inspection organizations into one.
Seepaluce
|
|

08-20-2007, 07:56 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Barrington, IL
Posts: 396
|
|
|
Re: Clearance for an air conditioner
My rule of thumb is 4 feet min., unless otherwise specified by manuf.
__________________
Eric Barker
Moraine Woods Consulting, Inc.
Barrington, IL
|
|

08-20-2007, 09:52 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Canandaigua New York
Posts: 131
|
|
|
Re: Clearance for an air conditioner
Depending on the model the clearances are different. The York units have 2 clearances depending on the model. The min. height clearance is 48" and the other units have a 60" clearance. I imagine that Carrier might have the same situation.
__________________
Well thats my 2 cents.
Brian Kelly
Kelly Home Inspections
|
|

08-20-2007, 09:53 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Peoria Arizona
Posts: 24
|
|
|
Re: Clearance for an air conditioner
This Carrier unit calls for 48".
http://www.docs.hvacpartners.com/idc/groups/public/documents/techlit/24aba-1si.pdf?SMSESSION=$SM$%2f0I2fGDwN1Zlj7kbsZLBulJkU7 rgN4715MJJQ%2f5bOUZaib5ISfLLSZud97Ep2%2flDLafmO0rd itJMoSG5wVnR23tedmJ3nGkE%2f9htGsLWvLTURlvnexNFXRu1 %2f1RUZtptHMBVshWYCTwLayREgs1nw9t0SvfxLRcX54%2bGgv nrJKTVnJburqdOB0iYBSK9%2b%2bwD26y5aBBLTs4%2feI09ib 5kI%2f1BA52h399g8QBrePd%2fMIyVXUn25vMcZx97PbJ0Ro9i UVqn452XBvzxJsn9p85uHcmRQyoANtqMb8AXkaD4Ipv2M4%2f9 1OocsH5Lb8zYOIT9307FpSU9HEw%3d
Jeff Euriech
Peoria Arizona
Last edited by Jeff Euriech : 08-20-2007 at 09:58 AM.
|
|

08-20-2007, 10:14 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Canandaigua New York
Posts: 131
|
|
|
Re: Clearance for an air conditioner
Jeff what are the letters and numbers after the .com???
__________________
Well thats my 2 cents.
Brian Kelly
Kelly Home Inspections
|
|

08-20-2007, 10:19 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Dallas, Texas
Posts: 1,579
|
|
|
Re: Clearance for an air conditioner
Brian, that is the full web address.
Copy and paste the entire string into you address bar and it takes you to the pertinent information. I just tried it and it works for me.
Jim
__________________
Jim Luttrall
Mr. Inspector.net, Inc.
Allen, Texas 75002
|
|

08-20-2007, 10:21 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Dallas, Texas
Posts: 1,579
|
|
|
Re: Clearance for an air conditioner
STEP 3.— Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30--in. clearance to
service end of unit and 48 in. above unit. For proper airflow, a
6--in. clearance on 1 side of unit and 12 in. on all remaining sides
must be maintained. Maintain a distance of 24 in. between units.
Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
Jim
__________________
Jim Luttrall
Mr. Inspector.net, Inc.
Allen, Texas 75002
|
|

08-20-2007, 11:41 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Colorado Springs, CO
Posts: 677
|
|
|
Re: Clearance for an air conditioner
You can make it easier for everyone by creating a link to the site like this:
Carrier Installation Instructions
To create a link simply type the following:
{url= WEB SITE ADDRESS (e.g., www.inspectionnews.net) } WEB SITE NAME {/url}
NOTE: Replace the { } brackets with [ ] brackets.
__________________
"Baseball is like church. Many attend but few understand." Leo Durocher
Bruce Breedlove
www.avaloninspection.com
|
|