You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 11-18-2007, 09:47 AM
Michael Thomas's Avatar
Michael Thomas Michael Thomas is offline
Member
 
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
Venting Issues
50,000 BTU GFAF and 40,000 BTU gas WH venting into 8" single wall pipe system passing through attic and meal chimney chase? What concerns (other than the birds nest, the rain cap and the single wall pipe passing through the attic) do others here see with this?
Attached Images
File Type: jpg 071117-1Vents.jpg (95.2 KB, 32 views)
File Type: jpg 071117-1Attic.jpg (99.9 KB, 32 views)
File Type: jpg 071117-1Chase.jpg (93.5 KB, 30 views)
File Type: jpg 071117-1Cap.jpg (93.3 KB, 27 views)
Reply With Quote
Home inspection
  #2 (permalink)  
Old 11-18-2007, 09:56 AM
John Arnold John Arnold is online now
Member
 
Join Date: Mar 2007
Location: Philadelphia PA
Posts: 1,317
Re: Venting Issues
Maybe it's the photo angle, but in the first one it looks like the wh flue pipe runs downhill.
Reply With Quote
  #3 (permalink)  
Old 11-18-2007, 11:18 AM
Bruce Breedlove's Avatar
Bruce Breedlove Bruce Breedlove is offline
Member
 
Join Date: Mar 2007
Location: Colorado Springs, CO
Posts: 677
Re: Venting Issues
I agree. Hard to tell from the photo angle but the WH flu does not appear to have proper slope.
__________________
"Baseball is like church. Many attend but few understand." Leo Durocher
Bruce Breedlove
www.avaloninspection.com
Reply With Quote
  #4 (permalink)  
Old 11-18-2007, 11:30 AM
Billy Stephens's Avatar
Billy Stephens Billy Stephens is offline
Member
 
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,602
Re: Venting Issues
Quote:
Originally Posted by John Arnold View Post
Maybe it's the photo angle, but in the first one it looks like the wh flue pipe runs downhill.
Or Flat, Rust on Flue Pipe, Evidence of moisture (several places) in the attic.
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
Reply With Quote
  #5 (permalink)  
Old 11-18-2007, 11:57 AM
Bob Harper's Avatar
Bob Harper Bob Harper is offline
Member
 
Join Date: Mar 2007
Location: Pa.
Posts: 577
Re: Venting Issues
No listed vent system to pass through unconditioned space
improper support
common vent oversized
vent not protected from damage in accessible portion of attic
severely restricted vent termination with unlisted hardware cloth doubled
oversized vent connector on WH (I'm guessing this WH has a 3" draft hood)
I doubt there is an attic insulation shield and we know there is no listed firestop because there is no listed venting.

The entire installation should be replaced with a properly sized and installed listed B-vent.
HTH
Bob
__________________
disgusted with some people on this forum. Out of here!
Reply With Quote
  #6 (permalink)  
Old 11-18-2007, 01:05 PM
Michael Thomas's Avatar
Michael Thomas Michael Thomas is offline
Member
 
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
Re: Venting Issues
Thanks,

Looks like I got it all - reading and study here and elsewhere must be doing some good!

There was an "insulation shield', and it was even pretty clean on the attic side (no pic), but here's the bottom.

As for the WH, it's going as Spackle does not not appear to be a permanent repair for leaking water heaters.
Attached Images
File Type: jpg 071117-1HVACShield.jpg (153.3 KB, 22 views)
File Type: jpg 071117-2WHBase.jpg (163.4 KB, 22 views)
Reply With Quote
  #7 (permalink)  
Old 11-18-2007, 01:50 PM
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,644
Re: Venting Issues
Is there a 30" wide path to and in front of that panel shown between the two units, with at 30" x 36" working space in front of that panel? (Okay, the walkway may be 24" wide, but the working space is 30" x 36".)
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Attic issues Zibby Swieca Attic Areas: Home Inspection and Commercial Inspection 13 10-14-2007 09:24 PM
Inspector should have noticed chimney issues - Contra Costa Times Brian Hannigan Fireplaces, Chimneys and Solid Fuel Burning Appliances: Home Inspection and Commercial Inspection 10 10-07-2007 06:17 PM
water heater venting Seth Hughes Plumbing System: Home Inspection and Commercial Inspection 6 08-05-2007 09:22 AM
Venting for gas fireplace Jon mackay Fireplaces, Chimneys and Solid Fuel Burning Appliances: Home Inspection and Commercial Inspection 3 06-19-2007 06:01 AM
Combustion air venting location Jeff Eastman Plumbing System: Home Inspection and Commercial Inspection 14 04-24-2007 07:43 PM


All times are GMT -7. The time now is 11:40 AM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger