You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!
If you have any problems with the registration process or your account login, please contact us.
Why join InspectionNews? Read the Testimonials
|
|

11-18-2007, 09:47 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
|
|
|
Venting Issues
50,000 BTU GFAF and 40,000 BTU gas WH venting into 8" single wall pipe system passing through attic and meal chimney chase? What concerns (other than the birds nest, the rain cap and the single wall pipe passing through the attic) do others here see with this?
|
|

11-18-2007, 09:56 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Philadelphia PA
Posts: 1,317
|
|
|
Re: Venting Issues
Maybe it's the photo angle, but in the first one it looks like the wh flue pipe runs downhill.
|
|

11-18-2007, 11:18 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Colorado Springs, CO
Posts: 677
|
|
|
Re: Venting Issues
I agree. Hard to tell from the photo angle but the WH flu does not appear to have proper slope.
__________________
"Baseball is like church. Many attend but few understand." Leo Durocher
Bruce Breedlove
www.avaloninspection.com
|
|

11-18-2007, 11:30 AM
|
 |
Member
|
|
Join Date: Aug 2007
Location: Memphis TN.
Posts: 1,602
|
|
|
Re: Venting Issues
Originally Posted by John Arnold
Maybe it's the photo angle, but in the first one it looks like the wh flue pipe runs downhill.
Or Flat, Rust on Flue Pipe, Evidence of moisture (several places) in the attic.
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
|
|

11-18-2007, 11:57 AM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Pa.
Posts: 577
|
|
|
Re: Venting Issues
No listed vent system to pass through unconditioned space
improper support
common vent oversized
vent not protected from damage in accessible portion of attic
severely restricted vent termination with unlisted hardware cloth doubled
oversized vent connector on WH (I'm guessing this WH has a 3" draft hood)
I doubt there is an attic insulation shield and we know there is no listed firestop because there is no listed venting.
The entire installation should be replaced with a properly sized and installed listed B-vent.
HTH
Bob
__________________
disgusted with some people on this forum. Out of here!
|
|

11-18-2007, 01:05 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
|
|
|
Re: Venting Issues
Thanks,
Looks like I got it all - reading and study here and elsewhere must be doing some good!
There was an "insulation shield', and it was even pretty clean on the attic side (no pic), but here's the bottom.
As for the WH, it's going as Spackle does not not appear to be a permanent repair for leaking water heaters.
|
|

11-18-2007, 01:50 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,644
|
|
|
Re: Venting Issues
Is there a 30" wide path to and in front of that panel shown between the two units, with at 30" x 36" working space in front of that panel? (Okay, the walkway may be 24" wide, but the working space is 30" x 36".)
|
|