You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!
If you have any problems with the registration process or your account login, please contact us.
Why join InspectionNews? Read the Testimonials
|
|

11-19-2007, 06:23 PM
|
|
Member
|
|
Join Date: Jul 2007
Location: Baton Rouge, La
Posts: 54
|
|
|
Air duct interface with slab
.........
Last edited by Clay White : 12-26-2007 at 11:11 AM.
|
|

11-19-2007, 06:27 PM
|
 |
Member
|
|
Join Date: Oct 2003
Location: Rockwall Texas
Posts: 2,396
|
|
|
Re: Air duct interface with slab
If they have ducts in the slab, that bit of missing sealant around that duct is the least of their worry.
|
|

11-19-2007, 07:23 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,644
|
|
|
Re: Air duct interface with slab
Originally Posted by Clay White
I fairly sure there are metal ducts in the slab.
Then this is worth repeating:
Originally Posted by Rick Hurst
If they have ducts in the slab, that bit of missing sealant around that duct is the least of their worry.
|
|

11-19-2007, 09:00 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Dallas, Texas
Posts: 1,579
|
|
|
Re: Air duct interface with slab
Rust, water infiltration, mold, musty, nasty, rodents, etc.
Other than that, they are just fine and are still allowed with certain restrictions if you are not in a flood prone area. 
__________________
Jim Luttrall
Mr. Inspector.net, Inc.
Allen, Texas 75002
|
|

11-19-2007, 09:02 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Santa Rosa, CA
Posts: 747
|
|
|
Re: Air duct interface with slab
Ducting in the slab is required to be completely encased. I cannot recall for sure, but I think it is a minimum of 2". However, they are often not encased and the bottom of the duct, in contact with soil, will rust out. In addition, as the duct is below grade, and concrete will often crack, the ducting could very well ship water into it.
Since this is a visual inspection, defer to an HVAC contractor.
__________________
The apostrophe troll.
|
|

11-19-2007, 09:35 PM
|
 |
Member
|
|
Join Date: Oct 2003
Location: Rockwall Texas
Posts: 2,396
|
|
|
Re: Air duct interface with slab
Ducts in the slab is just one of the contributors to the downfall use of Chlordane. Many termite control persons have actually drilled into the slab and accidentally pumped chemical into these ducts. Cleanup costs were outrageous and led to lawsuits.
I personally know of (1) case here in the DFW area.
If you like the musty smell, thats a reason to consider them I guess.
rick
|
|