You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 04-11-2007, 07:50 PM
Michael Thomas's Avatar
Michael Thomas Michael Thomas is offline
Member
 
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
Galvanizing Flaking Off Single Vent
What might cause this? Draft was fine, flame pattern was normal, no chemicals in area at time of inspection.
Attached Images
File Type: jpg INBoiler1.jpg (34.6 KB, 32 views)
File Type: jpg INBolier0.jpg (20.0 KB, 27 views)
Reply With Quote
  #2 (permalink)  
Old 04-12-2007, 12:43 PM
Bob Harper's Avatar
Bob Harper Bob Harper is offline
Member
 
Join Date: Mar 2007
Location: Pa.
Posts: 577
Re: Galvanizing Flaking Off Single Vent
While the draft may indeed be "fine", it could be too strong. There is a phenomenon known as the "curtain effect" with draft hood equipped appliances. The draft is so strong, the in rush of dilution air blocks the exhaust gases, which back up and vent out the base. This flaking could be from excessive heat buildup.

Then again, it could be from a bad batch of pipe. What other signs are there? Did you test with a CO analyzer around the base for backdrafting?

Weil-Macs can be a PIA to vent.
__________________
disgusted with some people on this forum. Out of here!
Reply With Quote
  #3 (permalink)  
Old 04-12-2007, 12:59 PM
Michael Thomas's Avatar
Michael Thomas Michael Thomas is offline
Member
 
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
Re: Galvanizing Flaking Off Single Vent
Bob,

Thanks as always. "Curtain effect" is new to me.

"Did you test with a CO analyzer around the base for backdrafting?"

Above my pay-grade (and level of competence) at this point.

Per tag the last service on this boiler was '01, there is a slight (water) leak at pump, and a service tech will be out Monday.

I'll be in the area and I'm going to meet him if possible, I'll see what he has to say.

BTW, that boiler is on the same chimney (let's hope not the same flue) the FP for which I just posted the damper picture.
Reply With Quote
Are inspection referrals from past clients important to you? If so, click here to get even more referrals!
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On



All times are GMT -7. The time now is 11:33 AM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger