You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 12-03-2007, 11:10 AM
Jeff Eastman Jeff Eastman is offline
Member
 
Join Date: Mar 2007
Location: gone
Posts: 245
Furnace clearance from rear closet wall
...........

Last edited by Jeff Eastman : 12-19-2007 at 02:36 PM.
Reply With Quote
  #2 (permalink)  
Old 12-03-2007, 11:23 AM
Michael Thomas's Avatar
Michael Thomas Michael Thomas is offline
Member
 
Join Date: Mar 2007
Location: Chicago, IL
Posts: 1,155
Re: Furnace clearance from rear closet wall
I would check manufacturer's instructions, can be zero.
Attached Images
File Type: jpg FurnaceClearances.jpg (36.7 KB, 17 views)
Reply With Quote
  #3 (permalink)  
Old 01-24-2008, 03:34 PM
max kasten max kasten is offline
Member
 
Join Date: Jan 2008
Location: PA
Posts: 6
Re: Furnace clearance from rear closet wall
The building code requires 30" on all sides see bellow

Appliances shall be accessible for inspection, service,
repair and replacement without removing permanent construction,
other appliances, or any other piping or ducts not
connected to the appliance being inspected, serviced, repaired or
replaced. A level working space at least 30 inches deep and 30
inches wide (762 mm by 762 mm) shall be provided in front of
the control side to service an appliance. Installation of room
heaters shall be permitted with at least an 18-inch (457 mm)
working space. A platform shall not be required for room heaters

Max Kasten
Building code official
Reply With Quote
  #4 (permalink)  
Old 01-24-2008, 03:42 PM
John Arnold John Arnold is online now
Member
 
Join Date: Mar 2007
Location: Philadelphia PA
Posts: 1,317
Re: Furnace clearance from rear closet wall
Quote:
Originally Posted by max kasten View Post
The building code requires 30" on all sides see bellow ...
...A level working space at least 30 inches deep and 30
inches wide (762 mm by 762 mm) shall be provided in front of
the control side to service an appliance....
I see where it says 30 inches in front. I don't see where it says 30 inches on all sides.
Reply With Quote
Are inspection referrals from past clients important to you? If so, click here to get even more referrals!
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Water heater clearance william siegel Plumbing System: Home Inspection and Commercial Inspection 4 10-06-2007 04:13 PM
Clearance for an air conditioner Kevin Luce Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 7 08-20-2007 11:41 AM
B Vent Window Clearance Jim Robinson Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 9 06-16-2007 09:11 AM
Who needs 6" of clearance for single wall Paul Kondzich Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 5 04-28-2007 07:17 PM
Propane regulator clearance Jim Luttrall Plumbing System: Home Inspection and Commercial Inspection 13 04-16-2007 08:30 AM


All times are GMT -7. The time now is 11:10 AM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger