|
|
|
|
Registration is FREE!... and will get rid of this top message
Welcome to InspectionNews.net.
You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but none of the pictures.
There are over 9,970 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, post new topics or reply to others, communicate privately with other members, respond to polls, upload content and access many other special features.
Registration is FREE for you because the sponsors pay your way. Please visit the sponsors often and let them know that you found them on InspectionNews!
Registration is FREE, fast and easy so please, join InspectionNews today!
Why join InspectionNews? Read the Testimonials
Looking for Education? We recommend Casey, O'Malley and Associates

If you have any problems with the registration process or your account login, please contact us.
|
|

01-21-2008, 01:56 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Cape Cod, Massachusetts
Posts: 143
|
|
|
Vent Pipe contacting Gas Pipe
Attached is an inspection I recently did.
The single walled heating vent pipe was in contact with the gas pipe.
I wrote it up as a a problem, but I couldn't find any reference in the code books. Anybody have any info on this?
Thanks
|
|

01-21-2008, 03:14 PM
|
|
|
|
Re: Vent Pipe contacting Gas Pipe
There's no problem with the gas pipe\vent connection. But . . .
The flexible gas appliance connector is not properly protected where it enters the side of the furnace. And . . .
There appears to be no gas shut-off valve for the furnace.
Aaron
|
|

01-21-2008, 03:18 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Cape Cod, Massachusetts
Posts: 143
|
|
|
Re: Vent Pipe contacting Gas Pipe
Aaron,
The shut off was above, but not shown in the picture.
Thanks for the feedback.
|
|

01-21-2008, 03:37 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Woodland Park, CO.
Posts: 188
|
|
|
Re: Vent Pipe contacting Gas Pipe
Am I wrong... that yellow gas flex line cannot enter the furnace cabinet????
__________________
Paul Kondzich
Altitude Home Inspection INC.
Woodland Park, CO.
|
|

01-21-2008, 05:14 PM
|
 |
Member
|
|
Join Date: Oct 2003
Location: Rockwall Texas
Posts: 3,655
|
|
|
Re: Vent Pipe contacting Gas Pipe
It looks like that flex enters the cabinet quite well.
You are correct in that it should not.
What i'm seeing is instead of hard pipe being installed, people are just wrapping the flex with a section of foam insulation or electrical tape thinking that is going to be acceptable. What realtor started that as being ok?
rick
|
|

01-21-2008, 05:34 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
|
|
|
Re: Vent Pipe contacting Gas Pipe
Also, I don't see any support strap for that vent where it goes horizontal and than there is the elbow.
|
|

01-21-2008, 05:51 PM
|
 |
Member
|
|
Join Date: Aug 2007
Location: Memphis TN.
Posts: 2,278
|
|
|
Re: Vent Pipe contacting Gas Pipe
I'm more concerned about the slope (or lack of on the first section of Flue Pipe!).
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
|
|

01-21-2008, 07:07 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
|
|
|
Re: Vent Pipe contacting Gas Pipe
Originally Posted by Billy Stephens
I'm more concerned about the slope (or lack of on the first section of Flue Pipe!).
More than the lack of the first one foot not being a vertical rise?
(Looked like it was sloped to me, but, from that angle, and no support, maybe it 'was' vertical when I saw it and now it a dropped?  )
|
|

01-21-2008, 07:20 PM
|
 |
Member
|
|
Join Date: Aug 2007
Location: Memphis TN.
Posts: 2,278
|
|
|
Re: Vent Pipe contacting Gas Pipe
Originally Posted by Billy Stephens
I'm more concerned about the slope (or lack of on the first section of Flue Pipe!).
Originally Posted by Jerry Peck
More than the lack of the first one foot not being a vertical rise? 
Needs a NEW Flue System for sure, I'd take a CLOSE LOOK at all the Gas Appliances.
After all Dead Clients ( or ones that are hospitalized Can't( won't REFER YOU,) 
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
|
|

01-22-2008, 06:15 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Near Philly, Pa.
Posts: 815
|
|
|
Re: Vent Pipe contacting Gas Pipe
Good to see ya'll picking up on these defects:
-lack of minimum vent connector rise
-lack of support at either offset
-no sign of mechanical fasteners at each joint including attachment to furnace collar
-flexible appliance connector unprotected penetration of appliance cabinet ( some mfrs. may allow this is reasonable protected from chafing, blunt trauma or electrical bonding to cabinet.
-vent connector slope
What does it vent into? Is there a manifold with WH?
Bob
PS- ASHI show in New Orleans was pretty good, though low turnout
__________________
Keep the fire in the fireplace.
|
|

01-22-2008, 06:50 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
|
|
|
Re: Vent Pipe contacting Gas Pipe
Originally Posted by Bob Harper
-no sign of mechanical fasteners at each joint including attachment to furnace collar
Bob,
Some mechanical fasteners 'are' visible in that photo. The other joints are not visible or taped over and may (or may not) have mechanical fasteners in them.
|
|
| Thread Tools |
Search this Thread |
|
|
|
Posting Rules
|
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts
HTML code is Off
|
|
|
| Thread |
Thread Starter |
Forum |
Replies |
Last Post |
| Single wall pipe to b-vent vent question |
Brian E Kelly |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
5 |
12-19-2007 05:55 PM |
| Scary looking vent pipe. |
Trent Tarter |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
3 |
07-25-2007 05:38 PM |
| Australian Vent pipe |
wayne soper |
Plumbing System: Home Inspection and Commercial Inspection |
2 |
07-19-2007 06:08 AM |
| Vent pipe |
wayne soper |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
4 |
07-01-2007 06:39 PM |
| Flex vent pipe |
John Stephenson |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
7 |
05-29-2007 10:57 AM |
All times are GMT -7. The time now is 09:49 PM.
| | |
|