InspectionNews - Home Inspection



Registration is FREE!... and will get rid of this top message

Welcome to InspectionNews.net.

You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but none of the pictures.

There are over 9,970 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, post new topics or reply to others, communicate privately with other members, respond to polls, upload content and access many other special features.

Registration is FREE for you because the sponsors pay your way. Please visit the sponsors often and let them know that you found them on InspectionNews!

Registration is FREE, fast and easy so please, join InspectionNews today!

Why join InspectionNews? Read the Testimonials

Looking for Education? We recommend Casey, O'Malley and Associates
Home and Commercial Inspection Education

If you have any problems with the registration process or your account login, please contact us.

Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 01-21-2008, 01:56 PM
Ken Amelin Ken Amelin is offline
Member
 
Join Date: Mar 2007
Location: Cape Cod, Massachusetts
Posts: 143
Vent Pipe contacting Gas Pipe
Attached is an inspection I recently did.
The single walled heating vent pipe was in contact with the gas pipe.

I wrote it up as a a problem, but I couldn't find any reference in the code books. Anybody have any info on this?

Thanks
Attached Images
File Type: jpg heat vent touch.jpg (55.1 KB, 99 views)
Reply With Quote
Are inspection referrals from past clients important to you? If so, click here to get even more referrals!
  #2 (permalink)  
Old 01-21-2008, 03:14 PM
Aaron Miller
 
Posts: n/a
Re: Vent Pipe contacting Gas Pipe
There's no problem with the gas pipe\vent connection. But . . .

The flexible gas appliance connector is not properly protected where it enters the side of the furnace. And . . .

There appears to be no gas shut-off valve for the furnace.

Aaron
Reply With Quote
  #3 (permalink)  
Old 01-21-2008, 03:18 PM
Ken Amelin Ken Amelin is offline
Member
 
Join Date: Mar 2007
Location: Cape Cod, Massachusetts
Posts: 143
Re: Vent Pipe contacting Gas Pipe
Aaron,

The shut off was above, but not shown in the picture.
Thanks for the feedback.
Reply With Quote
  #4 (permalink)  
Old 01-21-2008, 03:37 PM
Paul Kondzich Paul Kondzich is offline
Member
 
Join Date: Mar 2007
Location: Woodland Park, CO.
Posts: 188
Re: Vent Pipe contacting Gas Pipe
Am I wrong... that yellow gas flex line cannot enter the furnace cabinet????
__________________
Paul Kondzich
Altitude Home Inspection INC.
Woodland Park, CO.
Reply With Quote
  #5 (permalink)  
Old 01-21-2008, 05:14 PM
Rick Hurst's Avatar
Rick Hurst Rick Hurst is offline
Member
 
Join Date: Oct 2003
Location: Rockwall Texas
Posts: 3,655
Re: Vent Pipe contacting Gas Pipe
It looks like that flex enters the cabinet quite well.

You are correct in that it should not.

What i'm seeing is instead of hard pipe being installed, people are just wrapping the flex with a section of foam insulation or electrical tape thinking that is going to be acceptable. What realtor started that as being ok?

rick
Reply With Quote
  #6 (permalink)  
Old 01-21-2008, 05:34 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
Re: Vent Pipe contacting Gas Pipe
Also, I don't see any support strap for that vent where it goes horizontal and than there is the elbow.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
  #7 (permalink)  
Old 01-21-2008, 05:51 PM
Billy Stephens's Avatar
Billy Stephens Billy Stephens is online now
Member
 
Join Date: Aug 2007
Location: Memphis TN.
Posts: 2,278
Re: Vent Pipe contacting Gas Pipe
I'm more concerned about the slope (or lack of on the first section of Flue Pipe!).
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
Reply With Quote
  #8 (permalink)  
Old 01-21-2008, 07:07 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
Re: Vent Pipe contacting Gas Pipe
Quote:
Originally Posted by Billy Stephens View Post
I'm more concerned about the slope (or lack of on the first section of Flue Pipe!).
More than the lack of the first one foot not being a vertical rise?

(Looked like it was sloped to me, but, from that angle, and no support, maybe it 'was' vertical when I saw it and now it a dropped? )
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
  #9 (permalink)  
Old 01-21-2008, 07:20 PM
Billy Stephens's Avatar
Billy Stephens Billy Stephens is online now
Member
 
Join Date: Aug 2007
Location: Memphis TN.
Posts: 2,278
Re: Vent Pipe contacting Gas Pipe
Quote:
Originally Posted by Billy Stephens View Post
I'm more concerned about the slope (or lack of on the first section of Flue Pipe!).
Quote:
Originally Posted by Jerry Peck View Post
More than the lack of the first one foot not being a vertical rise?
Needs a NEW Flue System for sure, I'd take a CLOSE LOOK at all the Gas Appliances.

After all Dead Clients ( or ones that are hospitalized Can't( won't REFER YOU,)
__________________
It Might have Choked Artie But it ain't gone'a choke Stymie!
Billy J. Stephens HI Service
Memphis TN.
Reply With Quote
  #10 (permalink)  
Old 01-22-2008, 06:15 PM
Bob Harper's Avatar
Bob Harper Bob Harper is online now
Member
 
Join Date: Mar 2007
Location: Near Philly, Pa.
Posts: 815
Re: Vent Pipe contacting Gas Pipe
Good to see ya'll picking up on these defects:
-lack of minimum vent connector rise
-lack of support at either offset
-no sign of mechanical fasteners at each joint including attachment to furnace collar
-flexible appliance connector unprotected penetration of appliance cabinet ( some mfrs. may allow this is reasonable protected from chafing, blunt trauma or electrical bonding to cabinet.
-vent connector slope

What does it vent into? Is there a manifold with WH?

Bob

PS- ASHI show in New Orleans was pretty good, though low turnout
__________________
Keep the fire in the fireplace.
Reply With Quote
  #11 (permalink)  
Old 01-22-2008, 06:50 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,293
Re: Vent Pipe contacting Gas Pipe
Quote:
Originally Posted by Bob Harper View Post
-no sign of mechanical fasteners at each joint including attachment to furnace collar
Bob,

Some mechanical fasteners 'are' visible in that photo. The other joints are not visible or taped over and may (or may not) have mechanical fasteners in them.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
F.I.R.E. provides fireplace education, consulting services, fire investigation and litigation support across the United States.
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Single wall pipe to b-vent vent question Brian E Kelly Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 5 12-19-2007 05:55 PM
Scary looking vent pipe. Trent Tarter Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 3 07-25-2007 05:38 PM
Australian Vent pipe wayne soper Plumbing System: Home Inspection and Commercial Inspection 2 07-19-2007 06:08 AM
Vent pipe wayne soper Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 4 07-01-2007 06:39 PM
Flex vent pipe John Stephenson Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 7 05-29-2007 10:57 AM

Alabama | Alaska | Arizona | Atlanta | Aurora | Austin | Baltimore | Boston | California | Cambridge | Cape Coral | Chandler | Charlotte | Chicago | Cincinnati | Clarksville | Cleveland | Colorado | Columbus | Connecticut | Dallas | Delaware | Denver | Detroit | Durham | El Paso | Eugene | Florida | Fort Worth | Fresno | Georgia | Gilbert | Hawaii | Henderson | Houston | Huntsville | Idaho | Illinois | Indiana | Indianapolis | Irvine | Jacksonville | Joliet | Kansas City | Knoxville | Lancaster | Las Vegas | Los Angeles | Louisiana | Louisville | Maine | Maryland | Massachusetts | Memphis | Mesa | Miami | Michigan | Milwaukee | Minneapolis | Minnesota | Miramar | Mississippi | Missouri | Montana | Nashville | Nebraska | Nevada | New Hampshire | New Jersey | New Mexico | New York | North Carolina | North Dakota | Oakland | Ohio | Oklahoma | Omaha | Ontario | Orange | Oregon | Orlando | Pennsylvania | Philadelphia | Phoenix | Pittsburgh | Plano | Portland | Port StLucie | Raleigh | Rhode Island | Roseville | Sacramento | Salem | San Antonio | San Diego | San Francisco | San Jose | Scottsdale | Seattle | Sioux falls | South Carolina | South Dakota | St Louis | Tampa | Tennessee | Texas | Thornton | Toledo | Tucson | Tulsa | Utah | Vancouver | Vermont | Virginia | West Virginia | Wichita | Wisconsin | Wyoming | Cost To Repair

All times are GMT -7. The time now is 09:49 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2009, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger