You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 04-27-2007, 03:13 PM
Paul Kondzich Paul Kondzich is offline
Member
 
Join Date: Mar 2007
Location: Woodland Park, CO.
Posts: 170
Who needs 6" of clearance for single wall
Found this today.........
Attached Images
File Type: jpg DSC01712.JPG (66.5 KB, 83 views)
Reply With Quote
Home inspection
  #2 (permalink)  
Old 04-27-2007, 04:59 PM
Eric Barker's Avatar
Eric Barker Eric Barker is online now
Member
 
Join Date: Mar 2007
Location: Barrington, IL
Posts: 395
Re: Who needs 6" of clearance for single wall
Single wall? In an attic? There's more than a clearance issue.
__________________
Eric Barker
Moraine Woods Consulting, Inc.
Barrington, IL
Reply With Quote
  #3 (permalink)  
Old 04-27-2007, 05:28 PM
Rick Hurst's Avatar
Rick Hurst Rick Hurst is offline
Member
 
Join Date: Oct 2003
Location: Rockwall Texas
Posts: 2,395
Re: Who needs 6" of clearance for single wall
Flue should be double-wall constructed where it passes through a ceiling or roof decking and have a (1) inch clearance from combustible material.

6" clearance? Not sure what your meaning.
__________________
Rick Hurst_Home Works Inspection Co_Rockwall TX
In the words of Mike Tyson.... "Everyone has a plan until they get hit inda mouf"
Reply With Quote
  #4 (permalink)  
Old 04-27-2007, 07:04 PM
dick whitfield
 
Posts: n/a
Re: Who needs 6" of clearance for single wall
Good catch....you saved a life or two that day!
Reply With Quote
  #5 (permalink)  
Old 04-27-2007, 11:13 PM
Paul Kondzich Paul Kondzich is offline
Member
 
Join Date: Mar 2007
Location: Woodland Park, CO.
Posts: 170
Re: Who needs 6" of clearance for single wall
Maybe I wasnt aware that single wall vent was not allowed in attic, my bad. But as far as the 6" rule as far as I know single wall vent has to be 6" from any combustibles. If anyone can educate me further I welcome it.
Reply With Quote
  #6 (permalink)  
Old 04-28-2007, 07:17 PM
Bob Harper's Avatar
Bob Harper Bob Harper is offline
Member
 
Join Date: Mar 2007
Location: Pa.
Posts: 577
Re: Who needs 6" of clearance for single wall
Vent connector clearances:
gas single walled- 6"
B-vent- 1"
Oil single walled-18" unless listing states 9"
L-vent- 6-9" per listing except for pellet venting
pellet L vent-1-3" depending upon listing
wood single walled-18"
wood double walled close clearance -6"
No single walled connectors outside the thermal envelope such as attics or crawl spaces. Too much condensation and weaker draft.
__________________
disgusted with some people on this forum. Out of here!
Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
White "powder" at furnace exhaust tube Terry Beck Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 0 04-26-2007 11:00 PM
Single Wall Window Installation Mike Drorbaugh Building Envelope: Home Inspection and Commercial Inspection 12 04-25-2007 07:03 PM
Propane regulator clearance Jim Luttrall Plumbing System: Home Inspection and Commercial Inspection 13 04-16-2007 08:30 AM
Porch Re-Roof - How Should This Be "Flashed" Michael Thomas Exterior Systems: Home Inspection and Commercial Inspection 23 04-14-2007 08:46 AM
Galvanizing Flaking Off Single Vent Michael Thomas Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 2 04-12-2007 12:59 PM


All times are GMT -7. The time now is 07:36 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger