You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!
If you have any problems with the registration process or your account login, please contact us.
Why join InspectionNews? Read the Testimonials
|
|

07-14-2008, 09:46 PM
|
|
Member
|
|
Join Date: Mar 2008
Location: Park City, Utah
Posts: 184
|
|
|
Another condensate question
AC is not that popular around here so I don't know as much as I should. Each one I see seems to be different. This was in an attic and the primary was draining into a vent. However, no secondary and no trap on primary. There was a pan with a safe T switch. Another unit in the basemet only has a primary line. What's up.
|
|

07-15-2008, 08:34 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 6,641
|
|
|
Re: Another condensate question
At least there is a trap there, but there should be an air gap between the condensate and the trap. And that condensate line should be supported.
Man, that flexible duct sure is pulled t-i-g-h-t!
As we've stated in the past - the secondary needs to be trapped and drained, such as to the auxiliary drain pan.
Is that unit setting down in that drain pan? Or is it an optical illusion in the photo?
|
|

07-15-2008, 09:59 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Dallas, Texas
Posts: 1,449
|
|
|
Re: Another condensate question
Wrong primary, wrong secondary.
Is that sewer vent open to the attic?
Both the primary AND the secondary drains should be trapped and vented DOWNSTREAM of the trap. The drain line should terminate through an air gap to an approved place of disposal, (not a vent stack)
Looks like this unit is a prime candidate to let sewer gas into the air stream.
It will also suck or blow air from the un-trapped condensate lines resulting in energy loss.
__________________
Jim Luttrall
Mr. Inspector.net, Inc.
Allen, Texas 75002
|
|

07-15-2008, 10:01 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Dallas, Texas
Posts: 1,449
|
|
|
Re: Another condensate question
At least there is a trap there
Where is that Jerry?
__________________
Jim Luttrall
Mr. Inspector.net, Inc.
Allen, Texas 75002
|
|

07-15-2008, 11:28 AM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 6,641
|
|
|
Re: Another condensate question
Originally Posted by Jim Luttrall
Where is that Jerry?
Jim,
At the vent where the condensate drain connects to the vent.
|
|

07-15-2008, 01:55 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Dallas, Texas
Posts: 1,449
|
|
|
Re: Another condensate question
Ahh, I see now, hidden behind. I guess I need to get one of those big monitors (or maybe a pair, one for each eye)!
__________________
Jim Luttrall
Mr. Inspector.net, Inc.
Allen, Texas 75002
|
|

07-15-2008, 02:30 PM
|
 |
Member
|
|
Join Date: Mar 2007
Location: Connecticut
Posts: 726
|
|
|
Re: Another condensate question
Looks like someone, Guess who? stepped on the pan edge. I wonder how much water it will hold now?
|
|

07-15-2008, 02:41 PM
|
|
Member
|
|
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 6,641
|
|
|
Re: Another condensate question
Originally Posted by wayne soper
Looks like someone, Guess who? stepped on the pan edge.
Wayne,
No, that is from the unit being down *IN* the pan, and the pan being too small. The unit is pushing the side of the pan out. You can just see the unit pushing against it in the photo.
Of course, though, that means the pan is too small.
|
|

07-15-2008, 06:24 PM
|
|
Member
|
|
Join Date: Mar 2008
Location: Park City, Utah
Posts: 184
|
|
|
Re: Another condensate question
Thanks guys. The pan was too small, you can't see what the back looked like.
|
|
| Thread Tools |
Search this Thread |
|
|
|
Posting Rules
|
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts
HTML code is Off
|
|
|
| Thread |
Thread Starter |
Forum |
Replies |
Last Post |
| Condensate switch |
Jim Luttrall |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
22 |
07-11-2008 04:33 PM |
| Condensate drain |
wayne soper |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
0 |
05-15-2008 12:12 PM |
| AC Condensate drain - related question |
Terry Beck |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
1 |
08-24-2007 05:44 PM |
| Condensate? |
dan orourke |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
6 |
06-03-2007 03:46 PM |
| Condensate Tray |
Vince Santos |
Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection |
3 |
06-03-2007 12:44 PM |
All times are GMT -7. The time now is 10:38 PM.
| | |
|