Hot Water Heater TP valve drain pipe
Hi, This is Manzoor
I have recently seen that in new homes they are using a flexible copper pipe in the drain line of the TP valve. I had always thought that this pipe has to be solid copper, steel or cpvc. Has any one else experieced this ? Is it code compliant to use flexible pipe?
Similar Threads:
-
04-08-2008, 05:47 PM #2
Re: Hot Water Heater TP valve drain pipe
Those flex type copper lines are reduced and not 3/4in. inside diameter as required.
Therefore they are not acceptable.
Rick
-
04-08-2008, 06:37 PM #3
Re: Hot Water Heater TP valve drain pipe
Ditto Rick. Refer IRC 2006 P2803.1(3)
Jerry McCarthy
Building Code/ Construction Consultant
-
04-20-2008, 09:32 AM #4
Re: Hot Water Heater TP valve drain pipe
Thank you for pointing out the reduction in the diameter of the pipe.I am surprised that the code inspectors don't consider this a problem.