    Default Minimum pitch for three tag composition shingles.

    My first post. What is the minimum pitch for standard installation of three tab shingles? Next what must be done if pitch is less and same shingles are used? Finally, how can I tell what was done?
    I'm told this is a place to get answers. Right?
    Inspection Referral SOC

  2. #2
    Join Date
    Mar 2007
    Location
    Philadelphia PA
    Posts
    3,173

    Default Re: Minimum pitch for three tag composition shingles.

    Welcome Lamar!

    From the 2003 IRC:

    R905.2 Asphalt shingles. The installation of asphalt shingles shall comply with the provisions of this section.
    - R905.2.1 Sheathing requirements. Asphalt shingles shall be fastened to solidly sheathed decks.
    - R905.2.2 Slope. Asphalt shingles shall only be used on roof slopes of two units vertical in 12 units horizontal (2:12) or greater. For roof slopes from two units vertical in 12 units horizontal (2:12) up to four units vertical in 12 units horizontal (4:12), double underlayment application is required in accordance with Section R905.2.7.

  3. #3
    Join Date
    Mar 2007
    Location
    Spring Hill (Nashville), TN
    Posts
    5,697

    Default Re: Minimum pitch for three tag composition shingles.

    Quote Originally Posted by Lamar Bruce View Post
    My first post. What is the minimum pitch for standard installation of three tab shingles? Next what must be done if pitch is less and same shingles are used? Finally, how can I tell what was done?
    I'm told this is a place to get answers. Right?
    Lamar, are you a home inspector?
    Scott Patterson, ACI
    Spring Hill, TN
    www.traceinspections.com

  4. #4
    Join Date
    Mar 2007
    Location
    Philadelphia PA
    Posts
    3,173

    Default Re: Minimum pitch for three tag composition shingles.

    Sorry. Is it Lamar Bruce, or Bruce Lamar?

  5. #5
    Lamar Bruce's Avatar
    Lamar Bruce Guest

    Default Re: Minimum pitch for three tag composition shingles.

    Thanks. It's Lamar Bruce, Bruce Inspections, LLC in Taylors, SC. Thought this was right, but just needed confirmation. Thanks again.

  6. #6
    Join Date
    Jul 2008
    Location
    Utah
    Posts
    383

    Smile Re: Minimum pitch for three tag composition shingles.

    I am a practicing Mechanical Engineer in Utah.

    The IRC may require 2;12 pitch but in areas of high snow loads and consistant freeze-thaw cycles this is considered less than adequate. Be sure to check local codes and ordinances.


Similar Threads

  1. Asbestos roof shingles
    By Jim McClendon in forum Roofing System: Home Inspection and Commercial Inspection
    Replies: 5
    Last Post: 07-19-2007, 12:00 PM
  2. beam interface with shingles
    By John Stephenson in forum Roofing System: Home Inspection and Commercial Inspection
    Replies: 13
    Last Post: 06-22-2007, 01:38 AM
  3. Fuzzy Shingles
    By Nolan Kienitz in forum Roofing System: Home Inspection and Commercial Inspection
    Replies: 4
    Last Post: 06-02-2007, 04:25 PM
  4. Jack flashing shingles at edges.
    By Eric Shuman in forum Roofing System: Home Inspection and Commercial Inspection
    Replies: 5
    Last Post: 05-08-2007, 05:31 AM
  5. Asphalt comp shingles
    By Jeff Eastman in forum Roofing System: Home Inspection and Commercial Inspection
    Replies: 6
    Last Post: 04-23-2007, 04:48 PM

Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •