Re: Gas meter in relations to A/C
National Fuel Gas Code 54-5.7.2.3 “Gas meters shall be located at least 3 ft. from sources of ignition.” Ignition is considered anything that can ignite gas, such as electric motors, switches, outlets and most exhaust/vent terminations such as furnace and/or dryer vent. 3 foot clearance also applies to windows that can be opened and/or crawlspace vents.
I measure from the gas port on the gas regulator