    Default Fire sprinkler system

    Can the main water valve be before the branch for the sprinklers? I thought the fire sprinklers had to branch before the valve to prevent the occupant from disabling the system.

    Kevin Teitel
    House-Pro Inspections

    Similar Threads:
    OREP Insurance

  2. #2
    Jeff Remas's Avatar
    Jeff Remas Guest

    Default Re: Fire sprinkler system

    yes and normally with a tamper valve that alarms when it is closed. Most are chained open with break away locks too.