AAV code
The plumber on a new construction told me that there was no height requirement for the AAV on the kitchen island. Just accessibility. I believe its 4 in. above the fixture drain and/or 4 in. above the horizontal branch drain. Right or wrong?
Similar Threads:
-
07-22-2009, 10:23 AM #2
Re: AAV code
You are right
-
07-22-2009, 02:04 PM #3
Re: AAV code
-
07-22-2009, 03:01 PM #4
Re: AAV code
Just to clarify...it's a minimum of 4". More is OK.
-