Results 1 to 3 of 3
Thread: CSST through wall
-
04-25-2011, 08:12 AM #1
CSST through wall
I came across a CSST line run through a chimney. The installer wrapped the pipe with some electrical tape before filling the hole with cement around it. Is this an acceptable "cushion"? Thanks in advance.
Similar Threads:
-
04-25-2011, 08:24 AM #2
Re: CSST through wall
Should be sleeved and correctly fire stopped
-
04-25-2011, 09:16 AM #3
Re: CSST through wall
I go directly to the manufacturer when I see suspect installlations such as this one. See Sections 4.3.8 and 4.3.9 for installation requirements (link below). In short: No, eletrical tape is not an adequate alternative to a compliant sleeve. Also, the CSST may not be routed through a chimney chase, IRC G2415.1 prohibits this.
http://www.gastite.com/include/langu..._D+I_Guide.pdf
I hope this helps. I have been hesitant about joining in because sometimes legitimate posts, good questions and good answers get beat up beyond recognition. (Fingers crossed)
Bookmarks