FLEX PIPE BETWEEN MAIN PRESSURE CONTROL VALVE
HEY ALL
first time i have ever seen this. they have installed a water heater flex pipe between main water intake pressure valve and second shut off valve. i know this can't be right. what do you think??
cvf
Similar Threads:
-
07-21-2011, 08:29 PM #2
Re: FLEX PIPE BETWEEN MAIN PRESSURE CONTROL VALVE
Charlie,
That is one of these: SharkBite® Flexible Water Heater Connectors | Cash Acme
-
07-22-2011, 03:40 AM #3
Re: FLEX PIPE BETWEEN MAIN PRESSURE CONTROL VALVE
JERRY
thanks, iknow it had sharkbite label on it. i had just never seen it installed , and didn't know if it was allowed. see something new everyday in this job
thanks
charlie
-
07-22-2011, 06:15 PM #4
Re: FLEX PIPE BETWEEN MAIN PRESSURE CONTROL VALVE
Charlie,
Keep in that, like the other SharkBite fittings, and other flexible piping, I doubt that is electrically continuous.
As such, that would need a bonding jumper across it from metal piping to metal piping to maintain the electrical bonding.
-
07-22-2011, 06:33 PM #5
Re: FLEX PIPE BETWEEN MAIN PRESSURE CONTROL VALVE
jerry
after looking at photo again, i do see a copper rod on left side of photo--did not check for at inspection. but maybe it is there. may not get back to property--but it is vacant and close to me--so maybe go check out tomorrow. take a look
thanks
charlie