Thread: Double Trap, Pre-existing
-
08-25-2007, 08:16 AM #1
Double Trap, Pre-existing
I have a situation where a p-trap was placed for the bath tub and 2 feet later the water enters a drum trap. The general building inspector says it was double trapped! It was all existing prior to the floor being opened yet I am being forced to change it anyway.
It is much easier to cut out the p-trap and leave the drum trap, however this will result in the vent being in front of the drum trap....
The never ending question, can I vent in front of the trap?
Similar Threads:
-
08-25-2007, 09:29 AM #2
Re: Double Trap, Pre-existing
Nick,
Leave the P trap, remove the drum trap.
The vent needs to be after the trap and drum traps are, to my knowledge, no longer allowed.
From the IRC.
- P3201.5 Prohibited trap designs.The following types of traps are prohibited:
- - 1. Bell traps.
- - 2. Separate fixture traps with interior partitions, except those lavatory traps made of plastic, stainless steel or other corrosion-resistant material.
- - 3. āSā traps.
- - 4. Drum traps.
- - 5. Trap designs with moving parts.
-
08-25-2007, 09:49 AM #3
Re: Double Trap, Pre-existing
Drum Traps and what they look like.
Jerry McCarthy
Building Code/ Construction Consultant
-
08-25-2007, 09:51 AM #4
Re: Double Trap, Pre-existing
Jerry Mc.,
Thanks, I've seen photos of the type in the second photo, but had not seen any like that shown in the first photo.
-
09-30-2011, 06:07 AM #5
Re: Double Trap, Pre-existing
this is a question about drum traps.I have one that is I believe brass and have removed the plug to look inside but its to dirty to see any thing,but it feels like when I put a screw driver in it that there is a plate half way down.Is this some type of screen to catch debris and can it be removed to clean under it.Thanks for any answers. Stan