Manabloc manifold...satisfy shutoff at fixture?
Does the Manabloc manifold located in the garage satisfy the requirement to have individual shutoff for fixtures (sink)?
The Pex line goes from the manifold to the sink's hot and cold supply faucet...no shutoff at the sink.
12IRC doesn't say the individual shutoff has to be "at" the fixture. I think it meets the requirement. Am I understanding this right?
-
01-18-2014, 08:45 PM #2
Re: Manabloc manifold...satisfy shutoff at fixture?
The code says that there should be a shut off vale at each fixture, or ... at a manifold and if at a manifold each valve is to be marked and identified as to which fixture it goes to.
From the 2012 IRC:
- P2903.8.5 Valving.
- - Fixture valves, when installed, shall be located either at the fixture or at the manifold. If valves are installed at the manifold, they shall be labeled indicating the fixture served.
-