You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 10-10-2008, 05:10 PM
Dave Hill's Avatar
Dave Hill Dave Hill is offline
Member
 
Join Date: Mar 2007
Location: Chandler, AZ
Posts: 40
Vent near gable
Hi Folks,

Just inspected a new home. Not allowed on the roof, so I couldn't take measurements. I did see a vent pipe about 1 1/2 feet under the gable vent. Per the P3103.5 (2006 IRC) you shouldn't have vents close to "air intakes" to the house. I just want a sanity check here (on the question only) Is the gable vent to the attic considered an air intake to the home, (I believe it is) but it's not like a window or door that goes into the living area. What's the call here? violation or not?
(No I don't do code inspections, but do like to keep the new builders in line)

Thanks!
Waiting to finish report, thanks for your speedy replies.
-Dave
__________________
Dave Hill
Buyers & Sellers Property Inspections LLC
WWW.BuyersSellersPi.Com
Reply With Quote
  #2 (permalink)  
Old 10-10-2008, 05:40 PM
Rick Hurst's Avatar
Rick Hurst Rick Hurst is offline
Member
 
Join Date: Oct 2003
Location: Rockwall Texas
Posts: 2,398
Re: Vent near gable
Was it a "sewer vent" or what?

What was the vent to?

Got any pics?

rick
Reply With Quote
  #3 (permalink)  
Old 10-10-2008, 06:09 PM
Dave Hill's Avatar
Dave Hill Dave Hill is offline
Member
 
Join Date: Mar 2007
Location: Chandler, AZ
Posts: 40
Re: Vent near gable
yes, it was a sewer vent. The one directly under the gable vent.
Thanks for your help!
Attached Images
File Type: jpg avent2.jpg (39.2 KB, 93 views)
__________________
Dave Hill
Buyers & Sellers Property Inspections LLC
WWW.BuyersSellersPi.Com
Reply With Quote
  #4 (permalink)  
Old 10-10-2008, 07:53 PM
wayne soper's Avatar
wayne soper wayne soper is offline
Member
 
Join Date: Mar 2007
Location: Connecticut
Posts: 831
Re: Vent near gable
Yes, Bad planning and should not have been allowed. Did you send the broker into the attic to sniff around?
Reply With Quote
  #5 (permalink)  
Old 10-10-2008, 08:20 PM
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,648
Re: Vent near gable
As the others have said - no, not allowed, must be 10 feet from or 2 feet higher than those soffit vents.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
Reply With Quote
  #6 (permalink)  
Old 10-10-2008, 09:27 PM
Dave Hill's Avatar
Dave Hill Dave Hill is offline
Member
 
Join Date: Mar 2007
Location: Chandler, AZ
Posts: 40
Re: Vent near gable
As always, thanks for the help!
Have a groovy weekend!

BTW, I already submitted the report saying it was not allowed, thanks for backing me up. 4th year as an inspector and it still helps to bounce ideas off of other professionals. The code books are great, but a little help in interpretation is priceless.
__________________
Dave Hill
Buyers & Sellers Property Inspections LLC
WWW.BuyersSellersPi.Com
Reply With Quote
  #7 (permalink)  
Old 10-11-2008, 07:43 PM
Eric Barker's Avatar
Eric Barker Eric Barker is offline
Member
 
Join Date: Mar 2007
Location: Barrington, IL
Posts: 396
Re: Vent near gable
I reported the same a year or so ago. Mold in that area of the attic. I took a beating on that one. Neither the "plumber" nor the "mold remediator" agreed with me. Oh well! No referrals as a result of that job.
Attached Images
File Type: jpg undersoffitvent.JPG (155.9 KB, 55 views)
__________________
Eric Barker
Moraine Woods Consulting, Inc.
Barrington, IL
Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Single wall pipe to b-vent vent question Brian E Kelly Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 5 12-19-2007 05:55 PM
Gable end bracing Wade Johnson Roofing System: Home Inspection and Commercial Inspection 5 10-10-2007 05:59 AM
Plastic power vent to metal vent at brick chimney Christopher Kovac Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 24 10-09-2007 03:30 PM


All times are GMT -7. The time now is 11:48 AM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger