You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 05-17-2007, 10:32 AM
wayne soper's Avatar
wayne soper wayne soper is offline
Member
 
Join Date: Mar 2007
Location: Connecticut
Posts: 831
condensate pump drainage
Why would you want to stick a consensate drain line into the waste line for the toilet above? Any codes here besides the stupid contractor code?Anyone seen this before?
Attached Images
File Type: jpg Linden 048.jpg (44.4 KB, 62 views)
Reply With Quote
Home inspection
  #2 (permalink)  
Old 05-17-2007, 12:57 PM
David Banks David Banks is offline
Member
 
Join Date: Mar 2007
Location: Southborough, MA
Posts: 964
Re: condensate pump drainage
Not allowed. Done because it is quick and dirty.
Code Check says.
No direct connection to waste or vent pipe.
No drilling(sattle fitting) of DWV pipes to accept condensate drain.
May drain to indirect receptor(Lav,tailpiece,tub overflow) UMC only.
__________________
Dave
Reply With Quote
  #3 (permalink)  
Old 05-17-2007, 03:49 PM
Jim Robinson's Avatar
Jim Robinson Jim Robinson is offline
Member
 
Join Date: Mar 2007
Location: New Mexico
Posts: 341
Re: condensate pump drainage
Great picture. Keep that one for the scrap book. I have never seen that before.
__________________
Jim Robinson
New Mexico, USA
Reply With Quote
  #4 (permalink)  
Old 05-17-2007, 05:35 PM
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,648
Re: condensate pump drainage
As the others have said, not allowed - it requires an air gap / indirect connection, and not there.

Wonder how much crap came out onto them when they drilled that hole?

That should have been a clue?

Maybe 'that's their sign'?
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
Reply With Quote
  #5 (permalink)  
Old 03-10-2008, 06:10 PM
Dennis Corbett
 
Posts: n/a
Re: condensate pump drainage
Because of capacity problems at both of our city's water and sewage treatment plants and the nasty properties of condensate, the discharge is required to be retained on the property. We also have expansive soils, so you need to dig a drywell, 2' by 2' by 2' and a minimum 3' from foundation, filled with 1 1/2" drain rock, covered by plastic and 6" of soil. 1 1/2" ABS or PVC to carry the discharge from an airbreak at the building to drywell.
Reply With Quote
  #6 (permalink)  
Old 03-10-2008, 08:08 PM
Joshua Hardesty Joshua Hardesty is offline
Member
 
Join Date: Mar 2007
Posts: 117
Re: condensate pump drainage
I'd also be a bit concerned by the apparently notched double, and the short 90 used on a verticle to horizontal transition.
Reply With Quote
Are inspection referrals from past clients important to you?
If so, click here to get even more referrals!
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Sewage ejection pump-GFCI? Mike Huppi Electrical Systems: Home Inspection and Commercial Inspection 13 06-23-2007 11:50 PM
Loud gurlging noises - sink/tub drainage John Stephenson Plumbing System: Home Inspection and Commercial Inspection 5 05-16-2007 09:57 PM
Heat Pump? David Banks Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 15 05-06-2007 02:04 PM
condensate drain routing Jeff Eastman Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 8 04-16-2007 08:49 PM
condensate drain connection dan orourke Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 2 04-12-2007 09:19 PM


All times are GMT -7. The time now is 11:47 AM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger