InspectionNews - Home Inspection



Registration is FREE!... and will get rid of this top message

Welcome to InspectionNews.net.

You are currently viewing InspectionNews as a guest which gives you limited access to view some discussions but none of the pictures.

There are over 9,970 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, post new topics or reply to others, communicate privately with other members, respond to polls, upload content and access many other special features.

Registration is FREE for you because the sponsors pay your way. Please visit the sponsors often and let them know that you found them on InspectionNews!

Registration is FREE, fast and easy so please, join InspectionNews today!

Why join InspectionNews? Read the Testimonials

Looking for Education? We recommend Casey, O'Malley and Associates
Home and Commercial Inspection Education

If you have any problems with the registration process or your account login, please contact us.

Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 09-15-2007, 09:37 AM
Nick Ostrowski Nick Ostrowski is online now
Member
 
Join Date: Mar 2007
Location: Spring City/Surrounding Philadelphia area
Posts: 1,212
Polybutylene or No
I saw these water supply pipes in a 14 year old townhome yesterday and I can't tell if they are ploybutylene or not. The name stamped on them is "Themoguard" but whe I do an internet search, the poly pipes are stated to have a name of "Thermoguard".

Do these look like polybutylene? I see very little of it in my travels.
Attached Images
File Type: jpg poly1.jpg (58.7 KB, 181 views)
File Type: jpg poly2.jpg (37.0 KB, 158 views)
File Type: jpg poly4.jpg (46.7 KB, 155 views)
Reply With Quote
United Infrared
  #2 (permalink)  
Old 09-15-2007, 10:12 AM
Bruce King Bruce King is offline
Member
 
Join Date: Mar 2007
Location: York SC Licensed in NC and SC
Posts: 392
Re: Polybutylene or No
yep, gray pipes are PB pipe with copper or brass crimps.
White one is PEX

If city water with chlorine, pipe will likely fail.
Reply With Quote
  #3 (permalink)  
Old 09-15-2007, 10:12 AM
Dom D'Agostino Dom D'Agostino is offline
Member
 
Join Date: Mar 2007
Location: Longwood, FL
Posts: 415
Re: Polybutylene or No
Most definitely poly.

Dom.
Reply With Quote
  #4 (permalink)  
Old 09-15-2007, 01:35 PM
Nick Ostrowski Nick Ostrowski is online now
Member
 
Join Date: Mar 2007
Location: Spring City/Surrounding Philadelphia area
Posts: 1,212
Re: Polybutylene or No
Thanks guys.
Reply With Quote
  #5 (permalink)  
Old 09-15-2007, 08:32 PM
Zach Cogburn Zach Cogburn is offline
Member
 
Join Date: Sep 2007
Location: Bel Air, MD
Posts: 3
Re: Polybutylene or No
I recently did an inspection where I found similar looking pipes except they were all wrapped in insulation. I noted that they appeared to be PB piping which has a known history of failure and recommended a licensed plumber. I am glad I trusted my instincts that it was in fact PB. Believe it or not, the buyer didn't seem to think it was that big of a deal.
Reply With Quote
  #6 (permalink)  
Old 09-15-2007, 08:45 PM
Nick Ostrowski Nick Ostrowski is online now
Member
 
Join Date: Mar 2007
Location: Spring City/Surrounding Philadelphia area
Posts: 1,212
Re: Polybutylene or No
Zach, I once had a client who thought a 10+ foot long horizontal crack on an interior concrete block foundation wall with inward bowing was "normal settlement" and not worthy of the cost for a structural engineer.

We can lead the horses to water but can't make them drink.
Reply With Quote
  #7 (permalink)  
Old 09-16-2007, 02:33 PM
Jerry Peck's Avatar
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 14,297
Re: Polybutylene or No
Don't forget that white plastic dryer duct (or whatever it is being used for) is not allowed to be used for dryer duct (or whatever it is being used for).
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
www.AskCodeMan.com
Reply With Quote
  #8 (permalink)  
Old 09-16-2007, 04:32 PM
Sheryl Davidson Sheryl Davidson is offline
Member
 
Join Date: Aug 2007
Location: Alabama
Posts: 23
Re: Polybutylene or No
Definately PB pipe. I have inspected PB claims for the class action suit these are under. You might want to alert the customer that these are under suit and may be able to qualify for a replumb. The dates for filing the claim vary dependant on house age, etc. so the customer should look up the information online. CPRC, Inc. (default page)
Reply With Quote
  #9 (permalink)  
Old 09-16-2007, 08:44 PM
Bruce King Bruce King is offline
Member
 
Join Date: Mar 2007
Location: York SC Licensed in NC and SC
Posts: 392
Re: Polybutylene or No
Has anyone found any good proof that PB pipe with the updated fittings AND on well water without chlorine is actually an issue?

All of the PB info I can find only pertains to plastic fittings and chlorine issues with this pipe.

Many inspectors may choose (or be required by the state) to report the same verbiage on all PB installations but there is this particular setup that has not been addressed at all it.
Reply With Quote
  #10 (permalink)  
Old 09-17-2007, 07:04 AM
Scott Patterson's Avatar
Scott Patterson Scott Patterson is offline
Member
 
Join Date: Mar 2007
Location: Spring Hill (Nashville), TN
Posts: 2,806
Re: Polybutylene or No
Quote:
Originally Posted by Bruce King View Post
Has anyone found any good proof that PB pipe with the updated fittings AND on well water without chlorine is actually an issue?

All of the PB info I can find only pertains to plastic fittings and chlorine issues with this pipe.

Many inspectors may choose (or be required by the state) to report the same verbiage on all PB installations but there is this particular setup that has not been addressed at all it.
I had PB in my home that I lived in for fifteen years. Never had a problem with the PB pipe. All of the fittings and crimps were copper. I was on city water that was chlorinated. I'm not so sure that chlorine is the main culprit. Many chemicals are added to the water during the cleaning process. Our water was from a deep well and all the was added was chlorine. Ammonia is added as well as this keeps the chlorine in the water longer.
__________________
Scott Patterson
Spring Hill, TN
http://www.traceinspections.com
Reply With Quote
  #11 (permalink)  
Old 09-17-2007, 10:46 AM
Randy Moore Randy Moore is offline
Member
 
Join Date: Jun 2007
Location: Hudson, FL
Posts: 13
Re: Polybutylene or No
I own a home built in 1986 that was plumbed with PB pipe and it was an immediate disaster. Our problem was not the pipe itself but the fittings at the pipe junctions. When the plumbers secured the pipe to the fittings with copper bands the fittings were cracking inside the pipes. The whole house was leaking everywhere and it was brand new. We got a small settlement from the class action suit but it was a nightmare. We still have a lot of PB in the house but it hasn't given us any more problems since the fittings were replaced 20 years ago.
__________________
Pristine Home Inspections, Hudson, FL
www.pristineinspections.net
Reply With Quote
  #12 (permalink)  
Old 09-17-2007, 12:30 PM
Zach Cogburn Zach Cogburn is offline
Member
 
Join Date: Sep 2007
Location: Bel Air, MD
Posts: 3
Re: Polybutylene or No
As an inspector, when I come across items like this, systems that have a known history of failure (PB piping, Fed Pacific breakers and boxes), I always note it in the report and recommend the system be further evaluated by a licensed professional. That way I have protected myself from any further issues. The decision is for the buyer to make. How does everyone else handle these sorts of things.
Reply With Quote
  #13 (permalink)  
Old 09-17-2007, 06:06 PM
Sheryl Davidson Sheryl Davidson is offline
Member
 
Join Date: Aug 2007
Location: Alabama
Posts: 23
Re: Polybutylene or No
Quote:
Originally Posted by Bruce King View Post
Has anyone found any good proof that PB pipe with the updated fittings AND on well water without chlorine is actually an issue?

All of the PB info I can find only pertains to plastic fittings and chlorine issues with this pipe.

Many inspectors may choose (or be required by the state) to report the same verbiage on all PB installations but there is this particular setup that has not been addressed at all it.

I can't say for sure anything about chemicals in the water, but what I can tell you is that I would estimate 90% of the leaks I found during inspections were at the fittings (both copper and plastic) on the hot water lines. Cold water lines did not seem to be as bad so I think perhaps the heat caused the pipes to expand too much causing splits at the fittings. I have also seen where pipes literally blew off the fittings. Nasty stuff indeed.
Reply With Quote
  #14 (permalink)  
Old 09-17-2007, 09:44 PM
Patrick Martinez Patrick Martinez is offline
Member
 
Join Date: Mar 2007
Location: Vancouver, Washington
Posts: 44
Re: Polybutylene or No
Nick,

those my friend are PB pipes...Check out this site...

Polybutylene Plumbing - What is Polybutylene?

Pat
Reply With Quote
  #15 (permalink)  
Old 09-17-2007, 09:51 PM
Bruce King Bruce King is offline
Member
 
Join Date: Mar 2007
Location: York SC Licensed in NC and SC
Posts: 392
Re: Polybutylene or No
Inspected a house recently where the seller is a plumber contractor.
He had PB with plastic fittings on a community well.

Some of the fittings had weeping evidence, white deposits.

He had the pressure adjusted to cycle between 35psi and 45 psi.
I think he was trying to prevent a major leak by lowering the pressure.

He agreed to get his crew out to replumb the house....

Most of the PB I see has the updated crimps with metal inserts.
Reply With Quote
  #16 (permalink)  
Old 09-17-2007, 10:20 PM
Patrick Martinez Patrick Martinez is offline
Member
 
Join Date: Mar 2007
Location: Vancouver, Washington
Posts: 44
Re: Polybutylene or No
Nick,

keep in mind, should you find the PB lines, emphasis shall be placed on maintaining the <80 psi requirement. Though this is code, emphasis in particular on the PB, it can become really bad news really quick.

All water supply systems should be maintained <80, also it is a good idea to recommend WH Expansion tanks to help prolong the life of the system through out the home.

Pat
Reply With Quote
  #17 (permalink)  
Old 09-18-2007, 07:38 AM
Nick Ostrowski Nick Ostrowski is online now
Member
 
Join Date: Mar 2007
Location: Spring City/Surrounding Philadelphia area
Posts: 1,212
Re: Polybutylene or No
Thanks Patrick. I had found that same site myself while doing a little research of my own. And as luck would have it, the 30 year old townhouse I looked at yesterday also had poly pipes.
Reply With Quote
FREA Home Inspector Insurance
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Polybutylene? Vince Santos Plumbing System: Home Inspection and Commercial Inspection 11 06-26-2007 06:26 PM

Alabama | Alaska | Arizona | Atlanta | Aurora | Austin | Baltimore | Boston | California | Cambridge | Cape Coral | Chandler | Charlotte | Chicago | Cincinnati | Clarksville | Cleveland | Colorado | Columbus | Connecticut | Dallas | Delaware | Denver | Detroit | Durham | El Paso | Eugene | Florida | Fort Worth | Fresno | Georgia | Gilbert | Hawaii | Henderson | Houston | Huntsville | Idaho | Illinois | Indiana | Indianapolis | Irvine | Jacksonville | Joliet | Kansas City | Knoxville | Lancaster | Las Vegas | Los Angeles | Louisiana | Louisville | Maine | Maryland | Massachusetts | Memphis | Mesa | Miami | Michigan | Milwaukee | Minneapolis | Minnesota | Miramar | Mississippi | Missouri | Montana | Nashville | Nebraska | Nevada | New Hampshire | New Jersey | New Mexico | New York | North Carolina | North Dakota | Oakland | Ohio | Oklahoma | Omaha | Ontario | Orange | Oregon | Orlando | Pennsylvania | Philadelphia | Phoenix | Pittsburgh | Plano | Portland | Port StLucie | Raleigh | Rhode Island | Roseville | Sacramento | Salem | San Antonio | San Diego | San Francisco | San Jose | Scottsdale | Seattle | Sioux falls | South Carolina | South Dakota | St Louis | Tampa | Tennessee | Texas | Thornton | Toledo | Tucson | Tulsa | Utah | Vancouver | Vermont | Virginia | West Virginia | Wichita | Wisconsin | Wyoming | Cost To Repair

All times are GMT -7. The time now is 03:37 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2009, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger