You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 01-13-2008, 06:13 AM
imported_John Smith imported_John Smith is offline
Member
 
Join Date: Mar 2007
Location: Alvin Texas
Posts: 367
Low water flow at fixtures
I recently did an inspection on a 2 year old, 3 story townhome with copper plumbing. Water pressure at hose bibs was ~65 psig. The flow rate at the tub in the 2nd and 3rd floor bathrooms was just slightly > than 2 gpm. My understanding is that flow should be a least 4 gpm at bathtubs. Any suggestions on how this individual can get the flow increased to these areas?
Reply With Quote
Home inspection
  #2 (permalink)  
Old 01-13-2008, 06:43 AM
Nick Ostrowski Nick Ostrowski is offline
Member
 
Join Date: Mar 2007
Location: Spring City/Surrounding Philadelphia area
Posts: 762
Re: Low water flow at fixtures
John, did you check to see if the shut-off valves on the water supply lines to the tubs were totally open?
Reply With Quote
  #3 (permalink)  
Old 01-13-2008, 08:47 AM
Dom D'Agostino Dom D'Agostino is offline
Member
 
Join Date: Mar 2007
Location: Longwood, FL
Posts: 307
Re: Low water flow at fixtures
Most modern shower and bath valves have flow reducing devices to provide around 2 GPM. There may not be anything wrong.
Reply With Quote
  #4 (permalink)  
Old 01-13-2008, 10:32 AM
Rick Hurst's Avatar
Rick Hurst Rick Hurst is offline
Member
 
Join Date: Oct 2003
Location: Rockwall Texas
Posts: 2,417
Re: Low water flow at fixtures
If the faucet handles are the single lever type and the house has been vacant for a while, you probably have some sediment in the valve restricting the faucet to open completely.

rick
Reply With Quote
  #5 (permalink)  
Old 01-13-2008, 12:17 PM
imported_John Smith imported_John Smith is offline
Member
 
Join Date: Mar 2007
Location: Alvin Texas
Posts: 367
Re: Low water flow at fixtures
Ill respond to everyone that responded to my original post.

Rick, you maybe on to something. The house has been vacant for a while. It was a foreclosure (seems I have been doing a lot of them lately). Do you think there is an easy way to clean it out?

Dom, Im curious about your statement regarding the flow reducing devices. Seems odd IRC requires 4 gpm, but you could have a flow reducing device to get it to 2 gpm.

Nick, I cant remember ever seeing a shut off valve in Houston on bath tubs. Typically they don't even put access panels behind the tubs/showers.
Reply With Quote
  #6 (permalink)  
Old 01-13-2008, 12:24 PM
Lee Nettnin's Avatar
Lee Nettnin Lee Nettnin is offline
Member
 
Join Date: Mar 2007
Location: Hamlin, New York
Posts: 91
Re: Low water flow at fixtures
I am not familiar with your area, but where I am,it is common to see pressure reducing valves on the line just after the water meter. The reducing valve sometimes has a screen on it and hard water will clog the screen, or the pressure reducer needs an adjustment or replacement. The outside water bibs are usually connected to the main line before the reducer to allow full pressure in the outside lines.
__________________
www.eagleeyeinspectionshome.com
Reply With Quote
  #7 (permalink)  
Old 01-13-2008, 01:35 PM
Rick Hurst's Avatar
Rick Hurst Rick Hurst is offline
Member
 
Join Date: Oct 2003
Location: Rockwall Texas
Posts: 2,417
Re: Low water flow at fixtures
John,

You can remove the handle by removing the hex screw on the bottom.

Then you'll see a small screw head on the end of the cartridge. Turn the brass piece by hand to the hot side. You can tap on the end of the screw lightly and it will shake free the sediment on it which is prevent it to open properly.

rick
__________________
Rick Hurst_Home Works Inspection Co_Rockwall TX
In the words of Mike Tyson.... "Everyone has a plan until they get hit inda mouf"
Reply With Quote
Are inspection referrals from past clients important to you? If so, click here to get even more referrals!
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Rudd #5 Multi-fin Continuous Flow Heater McDaniel Attic Areas: Home Inspection and Commercial Inspection 5 12-20-2007 06:03 PM
Exterior light fixtures and recept. outlets Jeff Eastman Electrical Systems: Home Inspection and Commercial Inspection 1 05-08-2007 05:39 PM
Flow guard CPVC David Banks Plumbing System: Home Inspection and Commercial Inspection 8 04-24-2007 08:15 AM
Flow restrictors affect shower temps - Chicago Daily Herald Brian Hannigan Inspection News From Around The Net 0 04-08-2007 12:00 PM


All times are GMT -7. The time now is 03:32 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger