You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 07-18-2008, 08:34 AM
Bob Lynett Bob Lynett is offline
Member
 
Join Date: Mar 2007
Location: Green Bay, WI
Posts: 14
Flue pipe/Draft hood installation
Has anyone ever seen this type of installation, I inspected a Wick manufactured home where the WH and furnace are installed in a laundry room area on the main floor. I have never seen the draft hood area installed so high above the WH. Everthing was drafting ok with a smoke test but I just didn't feel comfortable with this type of installation.
Attached Images
File Type: jpg 002.jpg (23.9 KB, 73 views)
File Type: jpg 010.jpg (27.9 KB, 61 views)
Reply With Quote
Home inspection
  #2 (permalink)  
Old 07-18-2008, 08:53 AM
John Arnold John Arnold is offline
Member
 
Join Date: Mar 2007
Location: Philadelphia PA
Posts: 1,168
Re: Flue pipe/Draft hood installation
That looks completely wrong, and I don't even see a draft hood in your photos.
Is it a forced vent? How did the vent connect to the top of the water heater?
Reply With Quote
  #3 (permalink)  
Old 07-18-2008, 09:06 AM
Bob Lynett Bob Lynett is offline
Member
 
Join Date: Mar 2007
Location: Green Bay, WI
Posts: 14
Re: Flue pipe/Draft hood installation
John,

The connection at the WH was connected flush to the unit, no venting there. I thought the hood or make shift hood looked funky so I recommend a plumber evaluate.
Reply With Quote
  #4 (permalink)  
Old 07-18-2008, 10:32 AM
David Banks David Banks is offline
Member
 
Join Date: Mar 2007
Location: Southborough, MA
Posts: 909
Re: Flue pipe/Draft hood installation
Never seen one of those but according to this PDF it acts similar to draft hood. See vent packages page 3.
http://www.lawsonmobilehomesupply.co...wtrheaters.pdf
__________________
Dave
Reply With Quote
  #5 (permalink)  
Old 07-18-2008, 11:22 AM
Bob Lynett Bob Lynett is offline
Member
 
Join Date: Mar 2007
Location: Green Bay, WI
Posts: 14
Re: Flue pipe/Draft hood installation
Thanks for the information. Page 3 states for propane gas and this heater used natural gas. I guess I am not sure if that matters. The description pretty muchs looks like what was installed in this manufactured home.
Reply With Quote
  #6 (permalink)  
Old 07-18-2008, 01:37 PM
DavidR's Avatar
DavidR DavidR is offline
Member
 
Join Date: May 2007
Location: Frankfort, KY
Posts: 155
Re: Flue pipe/Draft hood installation
Be careful with the smoke test, it in no way indicates an appliance is venting properly.
The only thing it shows is that room air is going out the draft hood at that point in time.

That still functions the same as a standard bell type draft hood the only problem is both designs are useless and a potential timebomb waiting to go off.

Especially in a laundry room with a dryer capable of exhausting up to 100 CFM to the outdoors.
The draft hood and flue then becomes a nice make up air system.
__________________
Measured Performance more than just a buzzword
Reply With Quote
  #7 (permalink)  
Old 07-18-2008, 02:00 PM
Bob Harper's Avatar
Bob Harper Bob Harper is offline
Member
 
Join Date: Mar 2007
Location: Pa.
Posts: 518
Re: Flue pipe/Draft hood installation
As always, check the listed instructions from the appliance and venting. They must be listed together. Even so, Davidr's points should not be taken lightly. Also, cross check against these units: American Water Heater Co. Recall

I just love mfrs. who include a claims form on their Products section of the website but no install manuals!

Bob
__________________
Keep the fire inside the fireplace!
IAFCI Regional Director & Certified Fireplace Inspector
Certified Master Hearth Professional & HPBA BoD
Reply With Quote
Home inspection
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Double draft hood Dennis R Plumbing System: Home Inspection and Commercial Inspection 3 10-20-2007 01:45 PM
WH vent to draft hood connection Clay White Plumbing System: Home Inspection and Commercial Inspection 5 10-19-2007 08:00 PM
WH draft hood, insulation clearance Jeff Eastman Plumbing System: Home Inspection and Commercial Inspection 2 07-25-2007 12:48 PM
carbon build up at draft hood - furnace Eric Shuman Heating, Ventilation, Air Conditioning (HVAC): Home Inspection and Commercial Inspection 5 07-21-2007 01:59 PM
insualation clearance from draft hood dan orourke Plumbing System: Home Inspection and Commercial Inspection 9 05-03-2007 06:24 PM


All times are GMT -7. The time now is 02:55 AM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger