You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 08-22-2007, 12:13 AM
Bruce Breedlove's Avatar
Bruce Breedlove Bruce Breedlove is offline
Member
 
Join Date: Mar 2007
Location: Colorado Springs, CO
Posts: 676
Plumbing Vent Roof Jack At Valley
Ordinarily I would blame a lazy or inattentive plumber for placing a plumbing vent so close to a roof valley. But in this case this was an existing vent that years later ended up too close to a valley that was created when a rear addition was built.

Anyway, the valley flashing was stepped and notched to accomodate the roof jack flashing. Does anyone see a problem with the flashing for the roof jack encroaching into the valley? What comments would you make?
Attached Images
File Type: jpg R04.JPG (79.5 KB, 38 views)
__________________
"Baseball is like church. Many attend but few understand." Leo Durocher
Bruce Breedlove
www.avaloninspection.com
Reply With Quote
  #2 (permalink)  
Old 08-22-2007, 04:09 AM
David Banks David Banks is online now
Member
 
Join Date: Mar 2007
Location: Southborough, MA
Posts: 961
Re: Plumbing Vent Roof Jack At Valley
Bruce. I got this from Inspection News a while back. Just change chimney.

CHIMNEY IN VALLEY:
: There is supposed to be a 36" wide moisture barrier underlayment at all valleys, 18" to either side if installed correctly, Therefore no chimney(s), plumbing vent(s), or flue stack(s) should be placed within 18" of a valley. Penetrations to the moisture barrier may eventually leak and these areas will require further monitoring and sealant application if not relocated and installed correctly.
__________________
Dave
Reply With Quote
  #3 (permalink)  
Old 08-22-2007, 01:50 PM
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,600
Re: Plumbing Vent Roof Jack At Valley
We went through this recently, and it depends on how valleys are done in your area. (That's what was decided here.)

Many areas install a 16" wide valley metal in the valley, which extend out from the center 8" to each side, stay outside that valley metal and there is no problem.

Other areas install a 36" wide roll down the center of the valley, which extends out 18" ...

I'm not sure that the flashing in your photo is even 8" out from the center of the valley, and that is the minimum distance to clear the valley metal.
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
vent flashing/valley RobertSmith Plumbing System: Home Inspection and Commercial Inspection 18 08-06-2007 05:23 PM
Plumb vent near valley dan orourke Roofing System: Home Inspection and Commercial Inspection 5 07-06-2007 02:14 PM
Plumbing vent Jeff Eastman Plumbing System: Home Inspection and Commercial Inspection 1 06-27-2007 04:53 PM
Plumbing vent height John Stephenson Plumbing System: Home Inspection and Commercial Inspection 17 05-23-2007 01:44 PM
Roof Jack w/ Neoprene Boot At B Vent Bruce Breedlove Roofing System: Home Inspection and Commercial Inspection 6 04-03-2007 02:14 PM


All times are GMT -7. The time now is 06:53 AM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger