    Default stud notching, code clarification

    R602.6.1 states (Bold & underline is mine),

    "Any stud in an exterior wall or bearing partition may be cut or notched to a depth not exceeding 25 percent of its width..."

    From and ICC practice examine question:

    Q: Can a notch 1 1/2 inches deep be made in a nominal 2x6 exterior wall stud?

    A: No

    So what am I missing because I say yes....25% of 6 = 1.5" the code says not exceed 25% so being equal to 25% (1.5") should be fine.

    thanks

    Similar Threads:
    Inspection Referral

  2. #2
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: stud notching, code clarification

    Quote Originally Posted by Wendell Swedberg View Post
    So what am I missing because I say yes....25% of 6 = 1.5" the code says not exceed 25% so being equal to 25% (1.5") should be fine.

    thanks
    25% of 5.5 = 1.375

    You need to use the "actual" measurement for notching and boring.

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  3. #3
    Wendell Swedberg's Avatar
    Wendell Swedberg Guest

    Default Re: stud notching, code clarification

    Now for a bigger , silly question...how / where do you get 5.5"?

    Having said that, 1.375 inches is still less than 25% so either way (1.375 or 1.5 inches) , it's in compliance. Thus the test answer is wrong.


  4. #4
    Join Date
    Mar 2007
    Location
    Healdsburg, CA
    Posts
    1,741

    Default Re: stud notching, code clarification

    Wendell
    All stick framing lumber is sized 1/2" less then its call-out dimension. Back in the old days, pre WW II they where actually full sized, 2x4, 2x6, 2x8, etc., however that changed during the war and has been the protocol ever since. Jerry P's math is bang-on.

    Jerry McCarthy
    Building Code/ Construction Consultant

  5. #5
    Brandon Chew's Avatar
    Brandon Chew Guest

    Default Re: stud notching, code clarification

    Quote Originally Posted by Wendell Swedberg View Post
    Now for a bigger , silly question...how / where do you get 5.5"?

    Having said that, 1.375 inches is still less than 25% so either way (1.375 or 1.5 inches) , it's in compliance. Thus the test answer is wrong.
    Ditto what the tag-teaming Jerrys said.

    The key info was "nominal" 2x6, which is 5.5 inches actual dimension.

    The 25% limit means the notch can't be any deeper than 1.375... cutting one 1.5 is deeper than what is allowed.


  6. #6
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: stud notching, code clarification

    Quote Originally Posted by Wendell Swedberg View Post
    Having said that, 1.375 inches is still less than 25% so either way (1.375 or 1.5 inches) , it's in compliance. Thus the test answer is wrong.
    Wendell,

    The 1.375" I posted is the maximum permissible notch, not the 25%, a 1.5" notch exceeds that 1.375" maximum allowable notch.

    The test question is right.

    Added with edit: (Dang, should have read down to Brandon's post before I replied, Brandon already covered it.)

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  7. #7
    Join Date
    Feb 2008
    Location
    Chicago IL
    Posts
    2,048

    Default Re: stud notching, code clarification

    The question raises any interesting thought about trade practice. Plumbing walls typically have been framed 2x6 up here. Stacks running vertical of course not a problem. However the 1.5" vents and revents are drilled through the 2x6 studs for connection to the stack.
    Under that question plumbing walls would need to be 2x8 minimum. I've never seen that sofar. I find it unlikely any carpenter and plumber are going to get together on that.
    What has become somewhat more common is double framed walls, 2x4 on each side with space in between for piping.
    Just a comment.

    www.aic-chicago.com
    773/844-4AIC
    "The Code is not a ceiling to reach but a floor to work up from"

  8. #8
    Join Date
    Mar 2007
    Location
    Fletcher, NC
    Posts
    28,042

    Default Re: stud notching, code clarification

    Quote Originally Posted by Markus Keller View Post
    However the 1.5" vents and revents are drilled through the 2x6 studs for connection to the stack.
    Did you catch the difference in what you just stated and the original question?

    Original question: "cut or notched"

    You stated: "drilled through", i.e., "bored"

    Bored holes may be larger than "cutting and notching".

    Exterior and load bearing walls: cutting and notching = 25% / bored holes = 40%

    Interior and non-load bearing walls: cutting and notching = 40% / bored holes = 60%

    With an interior wall, non-load bearing, a bored hole in a 2x6 (5.5 inches actual) could be as large as 3.3 inches as long as the edge of the hole is no closer than 5/8" to the edge of the stud (basically centered in 2x6 stud).

    Does that makes thing work out better for what you see?

    Jerry Peck
    Construction/Litigation/Code Consultant - Retired
    www.AskCodeMan.com

  9. #9
    Join Date
    Feb 2008
    Location
    Chicago IL
    Posts
    2,048

    Default Re: stud notching, code clarification

    Ah yes, master Obiwan
    You are correct. I did not read the post that closely and 'see' "cut and notched" in opposition to my reply.
    I will retreat to the swamp to practice lifting my X-wing

    www.aic-chicago.com
    773/844-4AIC
    "The Code is not a ceiling to reach but a floor to work up from"

  10. #10
    Join Date
    Mar 2007
    Location
    Healdsburg, CA
    Posts
    1,741

    Default Re: stud notching, code clarification

    Diagrams are always helpful

    ***IMPORTANT*** You Need To Register To View Images ***IMPORTANT*** You Need To Register To View Images
    Jerry McCarthy
    Building Code/ Construction Consultant

Bookmarks

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •