You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 06-06-2008, 06:58 PM
Anthony Alderman's Avatar
Anthony Alderman Anthony Alderman is offline
Member
 
Join Date: Mar 2007
Location: Durham NC
Posts: 78
floor joist... need help
All right guys I need some help. I was in this 1920's 2story yesterday. The owner had tried to fix the structural problems to sell it. You can see in the photos that the help she got didn't help. My question is this is there a minimum that a joist can be cut before being placed on a ledger strip. Even with a joist hanger? The photos can explain it better than I.
Thanks
Tony
Attached Images
File Type: jpg joist1.JPG (96.5 KB, 37 views)
File Type: jpg joist2.JPG (109.4 KB, 35 views)
File Type: jpg joist3.JPG (101.2 KB, 35 views)
File Type: jpg joist4.JPG (110.6 KB, 34 views)
__________________
"A woman is only a woman, but a good cigar is a smoke".
Kipling
www.aahomeinspectionsllc.com
Reply With Quote
  #2 (permalink)  
Old 06-06-2008, 07:05 PM
Steve Frederickson Steve Frederickson is offline
Member
 
Join Date: Apr 2008
Location: Massachusetts
Posts: 14
Re: floor joist... need help
The joists without the hangers are no good because the notching is excessive.

The joists with the hangers are no good because the hangers aren't the right ones for that depth joist and they are too low to use all of the nail holes in the flanges. The rot (termites?) in the beam is also a problem, and the brick pier looks deteriorated.
Reply With Quote
  #3 (permalink)  
Old 06-06-2008, 07:10 PM
Jerry Peck Jerry Peck is offline
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 7,035
Re: floor joist... need help
Tony,

The biggest mistake they made (and it defeats anything and everything else they did) was to *not* replace that beam/girder and try to add new wood to the sides of it.

If nailed or lag bolted to the old beam/girder, what are the nails going into? Decayed/termite damaged wood?

If they tried to through bolt from new wood to new wood, the old would in the center defeats much or most of the strength they were trying to add with the new wood. Those two new wood peices need substantial and stable support between them, and that old decayed/termite damaged wood will not provide that.

Hopefully, Brandon Chew will comment further (and, hopefully, not shoot my thinking full of holes ).
__________________
Jerry Peck, Construction / Litigation Consultant
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
EastWestData (www.EastWestData.com )
Reply With Quote
  #4 (permalink)  
Old 06-06-2008, 07:26 PM
Ron Bibler Ron Bibler is online now
Member
 
Join Date: Mar 2008
Location: Healdsburg Ca
Posts: 564
Re: floor joist... need help
Tony all the above post are correct. If she is selling the home and is low on cash. sell the place as is and let the new owner deal with this condition.

If she has the cash. Then remove and replace the damage materials with correct construction. Contact a local termite inspector for a complete inspection report.

Best

Ron
Reply With Quote
  #5 (permalink)  
Old 06-06-2008, 07:43 PM
Anthony Alderman's Avatar
Anthony Alderman Anthony Alderman is offline
Member
 
Join Date: Mar 2007
Location: Durham NC
Posts: 78
Re: floor joist... need help
Well it seem that my guts were telling me the right things. Thanks. I was inspecting for a buyer. They had been told the the floor system had been worked on and was now fixed. So thats what they wanted me to look at first. Thats as far as the inspection went, they pulled the plug.
__________________
"A woman is only a woman, but a good cigar is a smoke".
Kipling
www.aahomeinspectionsllc.com
Reply With Quote
  #6 (permalink)  
Old 06-07-2008, 09:05 AM
Jerry McCarthy's Avatar
Jerry McCarthy Jerry McCarthy is offline
Member
 
Join Date: Mar 2007
Location: San Mateo, CA
Posts: 1,012
Re: floor joist... need help
Personally I fail to see any problems in those photos because that beefy brick pier is capable of supporting any load imposed and that kiln-dried original girder has little or no weight left in it.
__________________
Jerry McCarthy
Construction Consultant
www.expertbuildingconsultants.com
Reply With Quote
Home inspection
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Rim Joist Question Sean Bacon Exterior Systems: Home Inspection and Commercial Inspection 9 03-01-2008 09:39 AM
Floor Joist? Clay White Structural Components: Home Inspection and Commercial Inspection 4 11-03-2007 06:37 PM
Joist span wayne soper Exterior Systems: Home Inspection and Commercial Inspection 2 05-18-2007 12:08 PM
Scissor joist Mike Schulz Sub-Structure: Home Inspection and Commercial Inspection 9 04-11-2007 08:41 PM
Joist support Francis Turak Structural Components: Home Inspection and Commercial Inspection 14 04-04-2007 06:15 PM


All times are GMT -7. The time now is 11:58 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger