You are currently viewing InspectionNews as a guest which gives you limited access to view most discussions but not pictures. There are over 6,300 inspectors who have already joined. By joining InspectionNews you will be able to see the pictures, have access to post topics, communicate privately with other members, respond to polls, upload content and access many other special features. Registration is fast and simple so please, join InspectionNews today!

If you have any problems with the registration process or your account login, please contact us.

Why join InspectionNews? Read the Testimonials
Reply
 
LinkBack Thread Tools Search this Thread
  #1 (permalink)  
Old 07-13-2008, 08:29 PM
Bruce King Bruce King is offline
Member
 
Join Date: Mar 2007
Location: York SC Licensed in NC and SC
Posts: 235
attic flooring
Many new homes around here have trusses 24 on center, most of the attic floors are double thickness OSB (7/16) when furnaces and water heaters are present.

Some have single 7/16 OSB spanning 24" where the attic is only for storage.

The access on all examples is folding stairs or ceiling scuttles.

The single layer 7/16 has a span limit of 16 inches.

Any difference in IRC code because this area is only for storage?

In other words, is 7/16 OSB ever allowed to span 24 inches when used in storage areas without regular access?
Attached Images
File Type: jpg July 10 2008 018.jpg (130.0 KB, 88 views)
Reply With Quote
Home inspection
  #2 (permalink)  
Old 07-13-2008, 09:46 PM
Ted Menelly Ted Menelly is online now
Member
 
Join Date: Mar 2007
Location: Fort Worth, Texas
Posts: 705
Re: attic flooring
Personally I have always hated the 2 foot span. I am an older fart that use to build 16 on center even with trusses or at the very very least used 5/8 on the roof or walkways in attics.

I can't tell you how many times I stepped on 7/16 in an attic and scruuuuunch, crack. For storage I do not know the code I will have to look it up as well
__________________
Ted Menelly
"Castle"
Home Inspection Services
Reply With Quote
  #3 (permalink)  
Old 07-14-2008, 04:03 PM
Mitchell Toelle Mitchell Toelle is offline
Member
 
Join Date: Mar 2007
Location: Bakersfield, CA
Posts: 10
Re: attic flooring
Beware, any time you see sheathing on top of trusses where there is no mechanical sitting on it. Caution your client to never store any goods in that area. The bottom cord of most roof truss systems are engineered for only live load, not dead load, unless otherwise specified. If that sheathing is for access to work needed areas then it's okay, just for that, but not for storage of goods.

Hope that's helpful.

MPT
Reply With Quote
  #4 (permalink)  
Old 07-14-2008, 04:40 PM
Ted Menelly Ted Menelly is online now
Member
 
Join Date: Mar 2007
Location: Fort Worth, Texas
Posts: 705
Re: attic flooring
Quote:
Originally Posted by Mitchell Toelle View Post
Beware, any time you see sheathing on top of trusses where there is no mechanical sitting on it. Caution your client to never store any goods in that area. The bottom cord of most roof truss systems are engineered for only live load, not dead load, unless otherwise specified. If that sheathing is for access to work needed areas then it's okay, just for that, but not for storage of goods.

Hope that's helpful.

MPT
Yes and that also. Most new homes that builders use trusses on homes there will be a sign on the wall that it is not to be used as storage.
__________________
Ted Menelly
"Castle"
Home Inspection Services
Reply With Quote
  #5 (permalink)  
Old 07-14-2008, 07:30 PM
Steve Frederickson Steve Frederickson is offline
Member
 
Join Date: Apr 2008
Location: Massachusetts
Posts: 14
Re: attic flooring
Mitchel, I think you misspoke. Storage of goods would be considered live load, not dead load. Dead load is the weight of the building materials. All trusses are designed for dead load. Not all trusses are designed for live load on the bottom chord. However, based on the photo, I can almost guarantee that it was designed as a storage area.

Having said that, the question is above the sheathing. The sheathing should have a span rating stamped on the sheet. The rating would have the maximum span for allowed when used as floor sheathing, and teh max. span allwoed when used as rofo sheathing.

I hope this helps.
Reply With Quote
  #6 (permalink)  
Old 07-14-2008, 08:35 PM
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 6,524
Re: attic flooring
Quote:
Originally Posted by Bruce King View Post
Many new homes around here have trusses 24 on center, most of the attic floors are double thickness OSB (7/16) when furnaces and water heaters are present.

Some have single 7/16 OSB spanning 24" where the attic is only for storage.

The access on all examples is folding stairs or ceiling scuttles.

The single layer 7/16 has a span limit of 16 inches.

Any difference in IRC code because this area is only for storage?

In other words, is 7/16 OSB ever allowed to span 24 inches when used in storage areas without regular access?
Looking at IRC Table R503.2.1(1) for structural panels used for subfloor underlayment or, or for combination subfloor underlayment, I don't see anything less than 23/32 (3/4 inch) listed for a span of 24 inches.

The thinnest I see listed is 7/16 inch where used as a subfloor on 16 inch O.C. supports ... with "subfloor" being key, not to be used by itself 'as the floor'.

I also don't see any exception to the requirements for "floors" either, not for attic storage.

By the way, 2 layers of 7/16 inch does not meet the code either, not unless I am missing something???

I guess, if an engineer designed it with something less and could back it up with "rational analysis", and signed and sealed it, the local AHJ may (would not have to, but 'may') accept it.
__________________
Jerry Peck, Construction / Litigation Consultant
Ormond Beach, Florida
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
Reply With Quote
  #7 (permalink)  
Old 07-15-2008, 06:10 AM
Richard Stanley Richard Stanley is offline
Member
 
Join Date: Mar 2007
Location: Corpus Christi, TX
Posts: 311
Re: attic flooring
Too often I find 7/16 sheathing used for equipment access flooring in attices. Also the stamp is facing up that says "this side down" and also it is rated for sheathing - not flooring.
Reply With Quote
  #8 (permalink)  
Old 07-15-2008, 08:45 AM
Jerry Peck Jerry Peck is online now
Member
 
Join Date: Mar 2007
Location: Ormond Beach, Florida
Posts: 6,524
Re: attic flooring
Quote:
Originally Posted by Richard Stanley View Post
also it is rated for sheathing - not flooring.
It can be rated for sheathing, at those spans in the span rating, and used for "subflooring" at reduced spans - see the table I referenced.
__________________
Jerry Peck, Construction / Litigation Consultant
Ormond Beach, Florida
Construction Litigation Consultants, LLC ( www.ConstructionLitigationConsultants.com )
Reply With Quote
  #9 (permalink)  
Old 07-18-2008, 06:06 AM
Herb Scott Herb Scott is offline
Member
 
Join Date: Mar 2007
Location: Point Pleasant Pa.
Posts: 6
Re: attic flooring
If there is no evidence that the trusses were cut or modified than it is likely that they were designed for storage. I would put in my report that trusses are generally designed for dead loads only and recommend contacting the builder / truss manufacture to confirm that storage is permissible.
However, the bottom cord of the truss appears to be only 2x4 and even if it is 2x6. This means that under the OSB there will be either inadequate insulation, compressed insulation or (more likely) no insulation.
Lite storage on trusses never bothered me but when it affects the insulation you may be better off renting storage space.
Reply With Quote
  #10 (permalink)  
Old 07-18-2008, 06:56 PM
Bruce King Bruce King is offline
Member
 
Join Date: Mar 2007
Location: York SC Licensed in NC and SC
Posts: 235
Re: attic flooring
Picture shows attic flooring over the garage area.
2x4 lower chord, no insulation.

thanks for all the info guy's!
Reply With Quote
Home inspection
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Flooring Roof Trusses Michael Thomas Structural Components: Home Inspection and Commercial Inspection 5 03-16-2008 10:01 AM
Baked Vinyl Flooring Bruce Breedlove Building Interior: Home Inspection and Commercial Inspection 5 10-29-2007 01:01 PM
Flooring Inspectors Needed Ray Darrah Employment: Home Inspectors & Commercial Inspectors 2 10-20-2007 07:02 PM
Water penetration wood flooring Roni Litmanovic Building Interior: Home Inspection and Commercial Inspection 7 07-11-2007 03:59 PM
Deck flooring dan orourke Exterior Systems: Home Inspection and Commercial Inspection 4 06-20-2007 09:53 PM


All times are GMT -7. The time now is 06:31 PM.


Design by Vjacheslav Trushkin.
Powered by vBulletin® Version 3.6.5
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Search Engine Optimization by vBSEO 3.0.0 RC8
vB.Sponsors
All Rights Reserved. Hann Tech Marketing Link / InspectionNews.com / InspectionNews.net - No part of InspectionNews.net may be reproduced in any way, or by any means, without the prior written permission of InspectionNews.net. Use of any index or listing Software for the purpose of constructing a mailing list, creating promotional materials or producing a printed or electronic catalog of any kind is expressly forbidden without the prior written permission of InspectionNews.net - All text, graphics and design on InspectionNews.net is copyright by Hann Tech Marketing Links.
Ad Management by RedTyger